Table 647:
VMSQI technical data
Function
Range or value
Accuracy
Voltage positive sequence, U1
(10 to 300) V
±
0.5% of U at U ≤ 50 V
±
0.2% of U at U > 50 V
Voltage zero sequence, 3U0
(10 to 300) V
±
0.5% of U at U ≤ 50 V
±
0.2% of U at U > 50 V
Voltage negative sequence, U2
(10 to 300) V
±
0.5% of U at U ≤ 50 V
±
0.2% of U at U > 50 V
Phase angle
(10 to 300) V
±
0.5° at U ≤ 50 V
±
0.2° at U > 50 V
Table 648:
VNMMXU technical data
Function
Range or value
Accuracy
Voltage
(5 to 175) V
± 0.5% of U at U ≤ 50 V
± 0.2% of U at U > 50 V
Phase angle
(5 to 175) V
± 0.5° at U ≤ 50 V
± 0.2° at U > 50 V
16.2
Gas medium supervision SSIMG
16.2.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Gas medium supervision
SSIMG
-
63
16.2.2
Functionality
Gas medium supervision SSIMG is used for monitoring the circuit breaker condition.
Binary information based on the gas pressure in the circuit breaker is used as input
signals to the function. In addition, the function generates alarms based on received
information.
Section 16
1MRK502052-UEN B
Monitoring
890
Technical manual
Summary of Contents for Relion REG670
Page 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Page 2: ......
Page 44: ...38 ...
Page 58: ...52 ...
Page 80: ...74 ...
Page 106: ...100 ...
Page 482: ...476 ...
Page 548: ...542 ...
Page 570: ...564 ...
Page 600: ...594 ...
Page 608: ...602 ...
Page 630: ...624 ...
Page 862: ...856 ...
Page 1094: ...1088 ...
Page 1226: ...1220 ...
Page 1250: ...1244 ...
Page 1297: ...1291 ...