15.14.3
Function block
TIGAPC
IN
OUT
TIGAPC
IN
OUT
IEC14000013-1-en.vsd
IEC14000013 V1 EN
Figure 403:
TIGAPC function block
15.14.4
Signals
Table 603:
TIGAPC Input signals
Name
Type
Default
Description
IN
BOOLEAN
0
Input to integrator
Table 604:
TIGAPC Output signals
Name
Type
Description
OUT
BOOLEAN
Output from integrator
15.14.5
Settings
Table 605:
TIGAPC Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Off
On
-
-
Off
Operation Off / On
tDelay
0.000 - 600.000
s
0.001
1.000
Time delay to operate
tReset
0.000 - 600.000
s
0.001
1.000
Time delay to reset
15.14.6
Operation principle
In the pulse integrator TIGAPC, the time during which the input is high is integrated.
This means there is no output until the sum of the input pulses equals the set time delay
to operate. The output is deactivated when the input signal is FALSE and the time
delay to reset has elapsed.
1MRK502052-UEN B
Section 15
Logic
849
Technical manual
Summary of Contents for Relion REG670
Page 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Page 2: ......
Page 44: ...38 ...
Page 58: ...52 ...
Page 80: ...74 ...
Page 106: ...100 ...
Page 482: ...476 ...
Page 548: ...542 ...
Page 570: ...564 ...
Page 600: ...594 ...
Page 608: ...602 ...
Page 630: ...624 ...
Page 862: ...856 ...
Page 1094: ...1088 ...
Page 1226: ...1220 ...
Page 1250: ...1244 ...
Page 1297: ...1291 ...