14.5.5
Settings
Table 450:
SLGAPC Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Off
On
-
-
Off
Operation Off/On
NrPos
2 - 32
-
1
32
Number of positions in the switch
OutType
Pulsed
Steady
-
-
Steady
Output type, steady or pulse
tPulse
0.000 - 60.000
s
0.001
0.200
Operate pulse duration, in [s]
tDelay
0.000 - 60000.000
s
0.010
0.000
Time delay on the output, in [s]
StopAtExtremes
Disabled
Enabled
-
-
Disabled
Stop when min or max position is reached
14.5.6
Monitored data
Table 451:
SLGAPC Monitored data
Name
Type
Values (Range)
Unit
Description
SWPOSN
INTEGER
-
-
Switch position (integer)
14.5.7
Operation principle
The logic rotating switch for function selection and LHMI presentation (SLGAPC)
function has two operating inputs – UP and DOWN. When a signal is received on the
UP input, the function will activate the output next to the present activated output, in
ascending order (for example if the present activated output is P03 and one activates
the UP input then the output P04 will be activated). When a signal is received on the
DOWN input, the function will activate the output next to the present activated output,
in descending order (for example if the present activated output is P03 and one
activates the DOWN input then the output P02 will be activated). Depending on the
output settings the output signals can be steady or pulsed. In case of steady signals, the
output will be active till the time it receives next operation of UP/DOWN inputs. Also,
depending on the settings one can have a time delay between the UP or DOWN
activation signal positive front and the output activation.
Besides the inputs visible in the application configuration in the Application
Configuration tool, there are other possibilities that will allow an user to set the desired
position directly (without activating the intermediate positions), either locally or
remotely, using a “select before execute” dialog. One can block the function
operation, by activating the BLOCK input. In this case, the present position will be
kept and further operation will be blocked. The operator place (local or remote) is
specified through the PSTO input. If any operation is allowed the signal INTONE
from the Fixed signal function block can be connected. SLGAPC function block has
also an integer value output, that generates the actual position number. The positions
1MRK502052-UEN B
Section 14
Control
763
Technical manual
Summary of Contents for Relion REG670
Page 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Page 2: ......
Page 44: ...38 ...
Page 58: ...52 ...
Page 80: ...74 ...
Page 106: ...100 ...
Page 482: ...476 ...
Page 548: ...542 ...
Page 570: ...564 ...
Page 600: ...594 ...
Page 608: ...602 ...
Page 630: ...624 ...
Page 862: ...856 ...
Page 1094: ...1088 ...
Page 1226: ...1220 ...
Page 1250: ...1244 ...
Page 1297: ...1291 ...