14.3.6.1
Functionality
The Switch controller (SCSWI) initializes and supervises all functions to properly
select and operate switching primary apparatuses. The Switch controller may handle
and operate on one three-phase device or up to three one-phase devices.
14.3.6.2
Function block
BLOCK
EXE_OP
PSTO
EXE_CL
L_SEL
SEL_OP
L_OPEN
SEL_CL
L_CLOSE
SELECTED
SCSWI
AU_OPEN
RES_RQ
AU_CLOSE
START_SY
BL_CMD
CANC_SY
RES_GRT
POSITION
RES_EXT
OPENPOS
SY_INPRO
CLOSEPOS
SYNC_OK
POLEDISC
EN_OPEN
CMD_BLK
EN_CLOSE
L_CAUSE
XPOS1
POS_INTR
XPOS2
XOUT
XPOS3
IEC05000337-3-en.vsd
IEC05000337 V3 EN
Figure 334:
SCSWI function block
14.3.6.3
Signals
Table 408:
SCSWI Input signals
Name
Type
Default
Description
BLOCK
BOOLEAN
0
Block of function
PSTO
INTEGER
2
Operator place selection
L_SEL
BOOLEAN
0
Select signal from local panel
L_OPEN
BOOLEAN
0
Open signal from local panel
L_CLOSE
BOOLEAN
0
Close signal from local panel
AU_OPEN
BOOLEAN
0
Used for local automation function
AU_CLOSE
BOOLEAN
0
Used for local automation function
BL_CMD
BOOLEAN
0
Steady signal for block of the command
RES_GRT
BOOLEAN
0
Positive acknowledge that all reservations are
made
RES_EXT
BOOLEAN
0
Reservation is made externally
SY_INPRO
BOOLEAN
0
Synchronizing function in progress
SYNC_OK
BOOLEAN
0
Closing is permitted at set to true by the
synchrocheck
EN_OPEN
BOOLEAN
0
Enables open operation
EN_CLOSE
BOOLEAN
0
Enables close operation
Table continues on next page
Section 14
1MRK502052-UEN B
Control
716
Technical manual
Summary of Contents for Relion REG670
Page 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Page 2: ......
Page 44: ...38 ...
Page 58: ...52 ...
Page 80: ...74 ...
Page 106: ...100 ...
Page 482: ...476 ...
Page 548: ...542 ...
Page 570: ...564 ...
Page 600: ...594 ...
Page 608: ...602 ...
Page 630: ...624 ...
Page 862: ...856 ...
Page 1094: ...1088 ...
Page 1226: ...1220 ...
Page 1250: ...1244 ...
Page 1297: ...1291 ...