Dead Line Detection
IEC10000035-1-en.vsd
IEC10000035 V2 EN
Figure 292:
Simplified logic diagram for Dead Line detection part
13.2.7.4
Main logic
A simplified diagram for the functionality is found in figure
. The fuse failure
supervision function (FUFSPVC) can be switched on or off by the setting parameter
Operation
to
On
or
Off
.
For increased flexibility and adaptation to system requirements an operation mode
selector,
OpMode
, has been introduced to make it possible to select different operating
modes for the negative and zero sequence based algorithms. The different operation
modes are:
•
Off
. The negative and zero sequence function is switched off.
•
UNsINs
. Negative sequence is selected.
•
UZsIZs
. Zero sequence is selected.
•
UZsIZs OR UNsINs
. Both negative and zero sequence are activated and work in
parallel (OR-condition for operation).
•
UZsIZs AND UNsINs
. Both negative and zero sequence are activated and work in
series (AND-condition for operation).
•
OptimZsNs
. Optimum of negative and zero sequence current (the function that
has the highest magnitude of measured negative and zero sequence current will
be activated).
The delta function can be activated by setting the parameter
OpDUDI
to
On
. When
selected it operates in parallel with the sequence based algorithms.
Section 13
1MRK502052-UEN B
Secondary system supervision
616
Technical manual
Summary of Contents for Relion REG670
Page 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Page 2: ......
Page 44: ...38 ...
Page 58: ...52 ...
Page 80: ...74 ...
Page 106: ...100 ...
Page 482: ...476 ...
Page 548: ...542 ...
Page 570: ...564 ...
Page 600: ...594 ...
Page 608: ...602 ...
Page 630: ...624 ...
Page 862: ...856 ...
Page 1094: ...1088 ...
Page 1226: ...1220 ...
Page 1250: ...1244 ...
Page 1297: ...1291 ...