STRORHLD
BOOLEAN
Activated when function starts or HOLDACC input
is active
FREQOK
BOOLEAN
Indicates the system frequency within the
frequency band limits
VOLTOK
BOOLEAN
Indicates the system voltage within the voltage
band limits
10.4.5
Settings
Table 322:
FTAQFVR Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Off
On
-
-
Off
Operation Mode Off / On
tContinuous
0.0 - 6000.0
s
0.1
20.0
Continuous time limit for frequency band
limits
tAccLimit
10.0 - 90000.0
s
0.1
600.0
Accumulation time limit for frequency
band limits
FreqHighLimit
35.00 - 90.00
Hz
0.01
47.50
Frequency High limit value
FreqLowLimit
30.00 - 85.00
Hz
0.01
47.00
Frequency Low limit value
CBCheck
Disable
Enable
-
-
Enable
Enabling the generator start or stop
detection logic
CurrStartLevel
5.0 - 100.0
%IB
0.1
10.0
Threshold current value of generator in
percentage of base current
EnaVoltCheck
Disable
Enable
-
-
Enable
Enabling the voltage band limit check
UHighLimit
0.0 - 200.0
%UB
1.0
200.0
Voltage high limit for voltage band limit
check
ULowLimit
0.0 - 200.0
%UB
1.0
0.0
Voltage low limit for voltage band limit
check
Table 323:
FTAQFVR Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
GlobalBaseSel
1 - 12
-
1
1
Selection of one of the Global Base Value
groups
initTimeAcc
0.000 - 90000.000
s
0.001
0.0
Initial accumulated time when LOADINIT
command is executed
1MRK502052-UEN B
Section 10
Frequency protection
559
Technical manual
Summary of Contents for Relion REG670
Page 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Page 2: ......
Page 44: ...38 ...
Page 58: ...52 ...
Page 80: ...74 ...
Page 106: ...100 ...
Page 482: ...476 ...
Page 548: ...542 ...
Page 570: ...564 ...
Page 600: ...594 ...
Page 608: ...602 ...
Page 630: ...624 ...
Page 862: ...856 ...
Page 1094: ...1088 ...
Page 1226: ...1220 ...
Page 1250: ...1244 ...
Page 1297: ...1291 ...