9.5
Voltage differential protection VDCPTOV
9.5.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Voltage differential protection
VDCPTOV
-
60
9.5.2
Functionality
A voltage differential monitoring function is available. It compares the voltages from
two three phase sets of voltage transformers and has one sensitive alarm step and one
trip step.
9.5.3
Function block
IEC06000528-2-en.vsd
VDCPTOV
U3P1*
U3P2*
BLOCK
TRIP
START
ALARM
U1LOW
U2LOW
UL1DIFF
UL2DIFF
UL3DIFF
IEC06000528 V2 EN
Figure 254:
VDCPTOV function block
9.5.4
Signals
Table 291:
VDCPTOV Input signals
Name
Type
Default
Description
U3P1
GROUP
SIGNAL
-
Bus voltage
U3P2
GROUP
SIGNAL
-
Capacitor voltage
BLOCK
BOOLEAN
0
Block of function
Table 292:
VDCPTOV Output signals
Name
Type
Description
TRIP
BOOLEAN
Voltage differential protection operated
START
BOOLEAN
Start of voltage differential protection
ALARM
BOOLEAN
Voltage differential protection alarm
U1LOW
BOOLEAN
Loss of U1 voltage
Table continues on next page
Section 9
1MRK502052-UEN B
Voltage protection
528
Technical manual
Summary of Contents for Relion REG670
Page 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Page 2: ......
Page 44: ...38 ...
Page 58: ...52 ...
Page 80: ...74 ...
Page 106: ...100 ...
Page 482: ...476 ...
Page 548: ...542 ...
Page 570: ...564 ...
Page 600: ...594 ...
Page 608: ...602 ...
Page 630: ...624 ...
Page 862: ...856 ...
Page 1094: ...1088 ...
Page 1226: ...1220 ...
Page 1250: ...1244 ...
Page 1297: ...1291 ...