7.7.5
Settings
Table 116:
LEXPDIS Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Off
On
-
-
Off
Operation Off / On
OperationZ1
Off
On
-
-
On
Operation Off/On zone Z1
XoffsetZ1
-1000.00 - 1000.00
%
0.01
-10.00
Offset of Z1 circle top point along X axis in
% of Zbase
Z1diameter
0.01 - 3000.00
%
0.01
100.00
Diameter of impedance circle for Z1 in %
of Zbase
tZ1
0.00 - 6000.00
s
0.01
0.01
Trip time delay for Z1
OperationZ2
Off
On
-
-
On
Operation Off/On zone Z2
XoffsetZ2
-1000.00 - 1000.00
%
0.01
-10.00
Offset of Z2 circle top point along X axis in
% of Zbase
Z2diameter
0.01 - 3000.00
%
0.01
200.00
Diameter of impedance circle for Z2 in %
of Zbase
tZ2
0.00 - 6000.00
s
0.01
1.00
Trip time delay for Z2
Table 117:
LEXPDIS Group settings (advanced)
Name
Values (Range)
Unit
Step
Default
Description
DirSuperv
Off
On
-
-
Off
Operation Off/On for additional directional
criterion
XoffsetDirLine
-1000.00 - 3000.00
%
0.01
0.00
Offset of directional line along X axis in %
of Zbase
DirAngle
-180.0 - 180.0
Deg
0.1
-13.0
Angle between directional line and R-axis
in degrees
Table 118:
LEXPDIS Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
GlobalBaseSel
1 - 12
-
1
1
Selection of one of the Global Base Value
groups
MeasureMode
PosSeq
L1L2
L2L3
L3L1
-
-
PosSeq
Measuring mode (PosSeq, L1L2, L2L3,
L3L1)
Table 119:
LEXPDIS Non group settings (advanced)
Name
Values (Range)
Unit
Step
Default
Description
InvertCTcurr
No
Yes
-
-
No
Invert CT current
Section 7
1MRK502052-UEN B
Impedance protection
274
Technical manual
Summary of Contents for Relion REG670
Page 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Page 2: ......
Page 44: ...38 ...
Page 58: ...52 ...
Page 80: ...74 ...
Page 106: ...100 ...
Page 482: ...476 ...
Page 548: ...542 ...
Page 570: ...564 ...
Page 600: ...594 ...
Page 608: ...602 ...
Page 630: ...624 ...
Page 862: ...856 ...
Page 1094: ...1088 ...
Page 1226: ...1220 ...
Page 1250: ...1244 ...
Page 1297: ...1291 ...