Figure 83:
ZMFPDIS Characteristic for phase-to-phase measuring, ohm/loop
domain
The faulty loop in relation to the fault type can be presented as in Figure
. The main
intention with this illustration is to make clear how the fault resistive reach should be
interpreted and set. Note in particular that the setting RFPP always represents the total
fault resistance of the loop, regardless the fact that the fault resistance (arc) may be
divided into parts like for three-phase or phase-to-phase faults. The R1 + jX1 represent
the positive sequence impedance from the measuring point to the fault location.
Section 7
1MRK502052-UEN B
Impedance protection
218
Technical manual