7.1.7
Technical data
Table 74:
ZMHPDIS technical data
Function
Range or value
Accuracy
Number of zones, Ph-E
Max 4 with selectable direction -
Minimum operate current
(10–30)% of IBase
-
Positive sequence impedance,
Ph-E loop
(0.005–3000.000)
W
/phase
± 2.0% static accuracy
Conditions:
Voltage range: (0.1-1.1) x U
r
Current range: (0.5-30) x I
r
Angle: 85 degrees
Positive sequence impedance
angle, Ph-E loop
(10–90) degrees
Reverse reach, Ph-E loop
(Magnitude)
(0.005–3000.000) Ω/phase
Magnitude of earth return
compensation factor KN
(0.00–3.00)
Angle for earth compensation
factor KN
(-180–180) degrees
Dynamic overreach
<5% at 85 degrees measured
with CVT’s and 0.5<SIR<30
-
Definite time delay Ph-Ph and Ph-
E operation
(0.000-60.000) s
± 0.2% or ± 60 ms whichever is
greater
Operate time
22 ms typically
IEC 60255-121
Reset ratio
105% typically
-
Reset time at 0.5 to 1.5 x Zreach
Min = 30 ms
Max = 45 ms
-
7.2
Directional impedance element for mho
characteristic ZDMRDIR
7.2.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Directional impedance element for mho
characteristic
ZDMRDIR
S00346 V1 EN
21D
7.2.2
Functionality
The phase-to-earth impedance elements can be supervised by a phase unselective
directional function based on symmetrical components (option).
1MRK502052-UEN B
Section 7
Impedance protection
197
Technical manual
Summary of Contents for Relion REG670
Page 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Page 2: ......
Page 44: ...38 ...
Page 58: ...52 ...
Page 80: ...74 ...
Page 106: ...100 ...
Page 482: ...476 ...
Page 548: ...542 ...
Page 570: ...564 ...
Page 600: ...594 ...
Page 608: ...602 ...
Page 630: ...624 ...
Page 862: ...856 ...
Page 1094: ...1088 ...
Page 1226: ...1220 ...
Page 1250: ...1244 ...
Page 1297: ...1291 ...