Section 6
Differential protection
6.1
Transformer differential protection T2WPDIF and
T3WPDIF
6.1.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Transformer differential protection, two-
winding
T2WPDIF
3Id/I
SYMBOL-BB V1 EN
87T
Transformer differential protection,
three-winding
T3WPDIF
3Id/I
SYMBOL-BB V1 EN
87T
6.1.2
Functionality
The Transformer differential protection, two-winding T2WPDIF and Transformer
differential protection, three-winding T3WPDIF are provided with internal CT ratio
matching, vector group compensation and settable zero sequence current elimination.
The function can be provided with up to six three-phase sets of current inputs. All
current inputs are provided with percentage bias restraint features, making the IED
suitable for two- or three-winding transformer in multi-breaker station arrangements.
Two-winding applications
xx05000048.vsd
IEC05000048 V1 EN
two-winding power
transformer
xx05000049.vsd
IEC05000049 V1 EN
two-winding power
transformer with
unconnected delta
tertiary winding
Table continues on next page
1MRK502052-UEN B
Section 6
Differential protection
101
Technical manual
Summary of Contents for Relion REG670
Page 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Page 2: ......
Page 44: ...38 ...
Page 58: ...52 ...
Page 80: ...74 ...
Page 106: ...100 ...
Page 482: ...476 ...
Page 548: ...542 ...
Page 570: ...564 ...
Page 600: ...594 ...
Page 608: ...602 ...
Page 630: ...624 ...
Page 862: ...856 ...
Page 1094: ...1088 ...
Page 1226: ...1220 ...
Page 1250: ...1244 ...
Page 1297: ...1291 ...