SCFD decision
If the self-clearing fault is detected in at least one phase, the
PICKUP
and
TRIP
outputs
are set to "True". Also
SCDetect
in the monitored data is set to "True".
When one phase detects a fault, the algorithm waits for one cycle time and during this
period if the other two phases have detected a fault, the event is considered a three-phase
event and the
Event3Ph
in the monitored data is set to "True".
Activation of the
BLOCK
input deactivates all the binary outputs.
6.4.5
Signals
Table 291:
CFD Input signals
Name
Type
Default
Description
I_A
SIGNAL
0
Phase A current
I_B
SIGNAL
0
Phase B current
I_C
SIGNAL
0
Phase C current
BLOCK
BOOLEAN
0=False
Block signal for activating the blocking mode
Table 292:
CFD Output signals
Name
Type
Description
TRIP
BOOLEAN
Trip
PICKUP
BOOLEAN
Pickup
6.4.6
Settings
Table 293:
CFD Group settings
Parameter
Values (Range)
Unit
Step
Default
Description
PhPu
0...100000
10
500
Fault Pickup parameter Threshold
CyMulit
1...20
1
5
Fault detect threshold parameter
AbsMinLoad
0...300
10
100
Absolute min loading on the feeder
AdapPhPu
0=False
1=True
0=False
Adaptive phase pickup
Table 294:
CFD Non group settings
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=enable
5=disable
1=enable
Operation Disable / Enable
Section 6
1MRS240050-IB C
Supervision functions
380
REF615R
Technical Manual
Summary of Contents for RELION REF615R
Page 1: ... RELION PROTECTION AND CONTROL REF615R Technical Manual ...
Page 2: ......
Page 27: ...Section 18 Glossary 653 Table of contents REF615R 21 Technical Manual ...
Page 28: ...22 ...
Page 36: ...30 ...
Page 46: ...40 ...
Page 115: ...3 15 4 Settings 1MRS240050 IB C Section 3 Basic functions REF615R 109 Technical Manual ...
Page 118: ...112 ...
Page 318: ...312 ...
Page 388: ...382 ...
Page 456: ...450 ...
Page 520: ...514 ...
Page 652: ...646 ...
Page 656: ...650 ...
Page 658: ...652 ...
Page 663: ...657 ...