6.2.7
Settings
Table 282:
CCM Non group settings
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=enable
5=disable
1=enable
Operation Enable / Disable
Pickup value
0.05...0.20
xIn
0.01
0.05
Minimum trip current differential level
Max alarm current
1.00...5.00
xIn
0.01
1.50
Block of the function at high phase current
6.2.8
Monitored data
Table 283:
CCM Monitored data
Name
Type
Values (Range)
Unit
Description
I_DIFF
FLOAT32
0.00...40.00
xIn
Differential current
CCM
Enum
1=Enabled
2=blocked
3=test
4=test/blocked
5=Disabled
Status
6.2.9
Technical data
Table 284:
CCM Technical data
Characteristic
Value
Trip time
1)
<30 ms
1) Including the delay of the output contact
6.3
Fuse failure supervision 60
6.3.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Fuse failure supervision
SEQRFUF
FUSEF
60
Section 6
1MRS240050-IB C
Supervision functions
370
REF615R
Technical Manual
Summary of Contents for RELION REF615R
Page 1: ... RELION PROTECTION AND CONTROL REF615R Technical Manual ...
Page 2: ......
Page 27: ...Section 18 Glossary 653 Table of contents REF615R 21 Technical Manual ...
Page 28: ...22 ...
Page 36: ...30 ...
Page 46: ...40 ...
Page 115: ...3 15 4 Settings 1MRS240050 IB C Section 3 Basic functions REF615R 109 Technical Manual ...
Page 118: ...112 ...
Page 318: ...312 ...
Page 388: ...382 ...
Page 456: ...450 ...
Page 520: ...514 ...
Page 652: ...646 ...
Page 656: ...650 ...
Page 658: ...652 ...
Page 663: ...657 ...