4.3.1.7
Settings
Table 211:
81 Group settings
Parameter
Values (Range)
Unit
Step
Default
Description
Trip mode
1=Freq<
2=Freq>
3=df/dt
4=Freq< + df/dt
5=Freq> + df/dt
6=Freq< OR df/dt
7=Freq> OR df/dt
1=Freq<
Frequency protection trip mode selection
Pickup value Freq>
0.900...1.200
xFn
0.001
1.050
Frequency pickup value overfrequency
Pickup value Freq<
0.800...1.100
xFn
0.001
0.950
Frequency pickup value underfrequency
Pickup value df/dt
-0.200...0.200
xFn /s
0.005
0.010
Frequency pickup value rate of change
Trip Tm Freq
80...200000
ms
10
200
Trip delay time for frequency
Trip Tm df/dt
120...200000
ms
10
400
Trip delay time for frequency rate of change
Table 212:
81 Non group settings
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=enable
5=disable
1=enable
Operation Disable / Enable
Reset delay Tm Freq
0...60000
ms
1
0
Reset delay time for frequency
Reset delay Tm df/dt
0...60000
ms
1
0
Reset delay time for rate of change
4.3.1.8
Monitored data
Table 213:
81 Monitored data
Name
Type
Values (Range)
Unit
Description
PICKUP_DUR
FLOAT32
0.00...100.00
%
Pickup duration
ST_DUR_OFRQ
FLOAT32
0.00...100.00
%
Pickup duration
ST_DUR_UFRQ
FLOAT32
0.00...100.00
%
Pickup duration
ST_DUR_FRG
FLOAT32
0.00...100.00
%
Pickup duration
81
Enum
1=Enabled
2=blocked
3=test
4=test/blocked
5=Disabled
Status
Section 4
1MRS240050-IB C
Protection functions
270
REF615R
Technical Manual
Summary of Contents for RELION REF615R
Page 1: ... RELION PROTECTION AND CONTROL REF615R Technical Manual ...
Page 2: ......
Page 27: ...Section 18 Glossary 653 Table of contents REF615R 21 Technical Manual ...
Page 28: ...22 ...
Page 36: ...30 ...
Page 46: ...40 ...
Page 115: ...3 15 4 Settings 1MRS240050 IB C Section 3 Basic functions REF615R 109 Technical Manual ...
Page 118: ...112 ...
Page 318: ...312 ...
Page 388: ...382 ...
Page 456: ...450 ...
Page 520: ...514 ...
Page 652: ...646 ...
Page 656: ...650 ...
Page 658: ...652 ...
Page 663: ...657 ...