4.2.2.2
Function block
GUID-B4A78A17-67CA-497C-B2F1-BC4F1DA415B6-ANSI V1 EN
Figure 110:
Function block
4.2.2.3
Functionality
The three-phase undervoltage protection function 27 is used to disconnect from the
network devices, for example electric motors, which are damaged when subjected to
service under low voltage conditions. 27 includes a settable value for the detection of
undervoltage either in a single phase, two phases or three phases.
The function contains a blocking functionality. It is possible to block function outputs,
timer or the function itself, if desired.
4.2.2.4
Operation principle
The function can be enabled and disabled with the
Operation
setting. The corresponding
parameter values are “Enable” and “Disable”.
The operation of 27 can be described using a module diagram. All the modules in the
diagram are explained in the next sections.
GUID-9D762D4C-404B-4F4B-93A9-B1F071DF12F2-ANSI V1 EN
Figure 111:
Functional module diagram
Level detector
The fundamental frequency component of the measured three phase voltages are
compared phase-wise to the set
Pickup value
. If the measured value is lower than the set
value of the
Pickup value
setting, the level detector enables the phase selection logic
module. The
Relative hysteresis
setting can be used for preventing unnecessary
oscillations if the input signal slightly varies above or below the
Pickup value
setting.
Section 4
1MRS240050-IB C
Protection functions
230
REF615R
Technical Manual
Summary of Contents for RELION REF615R
Page 1: ... RELION PROTECTION AND CONTROL REF615R Technical Manual ...
Page 2: ......
Page 27: ...Section 18 Glossary 653 Table of contents REF615R 21 Technical Manual ...
Page 28: ...22 ...
Page 36: ...30 ...
Page 46: ...40 ...
Page 115: ...3 15 4 Settings 1MRS240050 IB C Section 3 Basic functions REF615R 109 Technical Manual ...
Page 118: ...112 ...
Page 318: ...312 ...
Page 388: ...382 ...
Page 456: ...450 ...
Page 520: ...514 ...
Page 652: ...646 ...
Page 656: ...650 ...
Page 658: ...652 ...
Page 663: ...657 ...