Figure 85:
Ground-fault situation in an isolated network
Directional ground-fault protection in a compensated network
In compensated networks, the capacitive fault current and the inductive resonance coil
current compensate each other. The protection cannot be based on the reactive current
measurement, since the current of the compensation coil would disturb the operation of
the protection relays. In this case, the selectivity is based on the measurement of the active
current component. The magnitude of this component is often small and must be increased
by means of a parallel resistor in the compensation equipment. When measuring the
resistive part of the zero-sequence current, the relay characteristic angle (RCA) should be
set to 0 degrees and the operation criteria to I
0
cos(φ) or phase angle.
A
B
C
C
0
Σ
I
01
Σ
I
02
-
Σ
I
02
I
ef
R
0
L
R
L
-
Σ
I
01
0
V
0
V
0
V
A070444-ANSI V1 EN
Figure 86:
Ground-fault situation in a compensated network
The Petersen coil or the grounding resistor may be temporarily out of operation. To keep
the protection scheme selective, it is necessary to update the
Characteristic angle
setting
1MRS240050-IB C
Section 4
Protection functions
REF615R
181
Technical Manual
Summary of Contents for RELION REF615R
Page 1: ... RELION PROTECTION AND CONTROL REF615R Technical Manual ...
Page 2: ......
Page 27: ...Section 18 Glossary 653 Table of contents REF615R 21 Technical Manual ...
Page 28: ...22 ...
Page 36: ...30 ...
Page 46: ...40 ...
Page 115: ...3 15 4 Settings 1MRS240050 IB C Section 3 Basic functions REF615R 109 Technical Manual ...
Page 118: ...112 ...
Page 318: ...312 ...
Page 388: ...382 ...
Page 456: ...450 ...
Page 520: ...514 ...
Page 652: ...646 ...
Page 656: ...650 ...
Page 658: ...652 ...
Page 663: ...657 ...