Characteristic
Value
Reset ratio
Typically 0.96
Retardation time
<35 ms
Trip time accuracy in definite time mode
±1.0% of the set value or ±20 ms
Trip time accuracy in inverse time mode
±5.0% of the theoretical value or ±20 ms
3)
Suppression of harmonics
DFT: -50 dB at f = n × f
n
, where n = 2, 3, 4, 5,…
1)
Measurement mode and Pol quantity = default, current before fault = 0.0 × I
n
, voltage before fault = 1.0 ×
V
n
, f
n
= 60 Hz, fault current in one phase with nominal frequency injected from random phase angle, results
based on statistical distribution of 1000 measurements
2) Includes the delay of the signal output contact
3) Maximum
Pickup value = 2.5 × I
n
,
Pickup value multiples in range of 1.5...20
4.1.4
Non-directional neutral overcurrent protection 51N/50N and
Non-directional ground fault protection 51G/50G
4.1.4.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Non-directional ground-fault protection,
low stage
EFLPTOC
Io>
51N/G
Non-directional ground-fault protection,
high stage
EFHPTOC
Io>>
50N/G-1/2
Non-directional ground-fault protection,
instantaneous stage
EFIPTOC
Io>>>
50N/G-3
4.1.4.2
Function block
A070432-ANSI V1 EN
Figure 78:
Function block
4.1.4.3
Functionality
The ground-fault function 51N/50N or 51G/50G is used as non-directional ground-fault
protection.
1MRS240050-IB C
Section 4
Protection functions
REF615R
161
Technical Manual
Summary of Contents for RELION REF615R
Page 1: ... RELION PROTECTION AND CONTROL REF615R Technical Manual ...
Page 2: ......
Page 27: ...Section 18 Glossary 653 Table of contents REF615R 21 Technical Manual ...
Page 28: ...22 ...
Page 36: ...30 ...
Page 46: ...40 ...
Page 115: ...3 15 4 Settings 1MRS240050 IB C Section 3 Basic functions REF615R 109 Technical Manual ...
Page 118: ...112 ...
Page 318: ...312 ...
Page 388: ...382 ...
Page 456: ...450 ...
Page 520: ...514 ...
Page 652: ...646 ...
Page 656: ...650 ...
Page 658: ...652 ...
Page 663: ...657 ...