4.1.1.5
Measurement modes
The function operates on four alternative measurement modes: "RMS", "DFT", "Peak-to-
Peak" and "P-to-P + backup". The measurement mode is selected with the setting
Measurement mode
.
Table 67:
Measurement modes supported by 51P/50P stages
Measurement mode
51P
50P-1/2
50P-3
RMS
x
x
DFT
x
x
Peak-to-Peak
x
x
P-to-P + backup
x
For a detailed description of the measurement modes, see the
4.1.1.6
Timer characteristics
51P/50P supports both DT and IDMT characteristics. The user can select the timer
characteristics with the
Operating curve type
and
Type of reset curve
settings. When the
DT characteristic is selected, it is only affected by the
Trip delay time
and
Reset delay time
settings.
The protection relay provides 16 IDMT characteristics curves, of which seven comply
with the IEEE C37.112 and six with the IEC 60255-3 standard. Two curves follow the
special characteristics of ABB praxis and are referred to as RI and RD. In addition to this,
a user programmable curve can be used if none of the standard curves are applicable. The
DT characteristics can be chosen by selecting the
Operating curve type
values "ANSI Def.
Time" or "IEC Def. Time". The functionality is identical in both cases.
The timer characteristics supported by different stages comply with the list in the IEC
61850-7-4 specification, indicate the characteristics supported by different stages:
Table 68:
Timer characteristics supported by different stages
Operating curve type
51P
50P-1/2
(1) ANSI Extremely Inverse
x
x
(2) ANSI Very Inverse
x
(3) ANSI Normal Inverse
x
x
(4) ANSI Moderately Inverse
x
(5) ANSI Definite Time
x
x
Table continues on next page
1MRS240050-IB C
Section 4
Protection functions
REF615R
117
Technical Manual
Summary of Contents for RELION REF615R
Page 1: ... RELION PROTECTION AND CONTROL REF615R Technical Manual ...
Page 2: ......
Page 27: ...Section 18 Glossary 653 Table of contents REF615R 21 Technical Manual ...
Page 28: ...22 ...
Page 36: ...30 ...
Page 46: ...40 ...
Page 115: ...3 15 4 Settings 1MRS240050 IB C Section 3 Basic functions REF615R 109 Technical Manual ...
Page 118: ...112 ...
Page 318: ...312 ...
Page 388: ...382 ...
Page 456: ...450 ...
Page 520: ...514 ...
Page 652: ...646 ...
Page 656: ...650 ...
Page 658: ...652 ...
Page 663: ...657 ...