Configuration of inputs and outputs of PCFCNT is made via PCM600.
On the Binary input module (BIM), the debounce filter default time is set to 1 ms, that
is, the counter suppresses pulses with a pulse length less than 1 ms. The input
oscillation blocking frequency is preset to 40 Hz meaning that the counter detects the
input to oscillate if the input frequency is greater than 40 Hz. Oscillation suppression is
released at 30 Hz. Block/release values for oscillation can be changed on the local HMI
and PCM600 under
Main menu/Configuration/I/O modules
.
The setting is common for all input channels on BIM, that is, if limit
changes are made for inputs not connected to the pulse counter, the
setting also influences the inputs on the same board used for pulse
counting.
18.2
Function for energy calculation and demand handling
ETPMMTR
SEMOD153638-1 v2
18.2.1
Identification
SEMOD175537-2 v4
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Function for energy calculation and
demand handling
ETPMMTR
W_Varh
-
18.2.2
Application
SEMOD175546-4 v5
Energy calculation and demand handling function (ETPMMTR) is intended for
statistics of the forward and reverse active and reactive energy. It has a high accuracy
basically given by the measurements function (CVMMXN). This function has a site
calibration possibility to further increase the total accuracy.
The function is connected to the instantaneous outputs of (CVMMXN) as shown in
figure
.
Section 18
1MRK 511 401-UUS A
Metering
566
Bay control REC670 2.2 ANSI
Application manual
Summary of Contents for Relion REC670
Page 1: ...RELION 670 SERIES Bay control REC670 Version 2 2 ANSI Application manual ...
Page 2: ......
Page 26: ...20 ...
Page 42: ...36 ...
Page 96: ...90 ...
Page 274: ...268 ...
Page 292: ...286 ...
Page 298: ...292 ...
Page 308: ...302 ...
Page 470: ...464 ...
Page 514: ...508 ...
Page 608: ...602 ...
Page 646: ...640 ...
Page 656: ...650 ...
Page 657: ...651 ...