The internal events in this list not only refer to faults in the IED, but also to other
activities, such as change of settings, clearing of disturbance reports, and loss of
external time synchronization.
The information can only be retrieved from the Parameter Setting software
package. The PC can be connected either to the port at the front or at the rear of the
IED.
These events are logged as internal events.
Table 19:
Events available for the internal event list in the IED
Event message:
Description
Generating signal:
INT--FAIL
Off
Internal fail status
INT--FAIL (reset event)
INT--FAIL
INT--FAIL (set event)
INT--WARNING
Off
Internal warning status
lNT--WARNING (reset event)
INT--WARNING
lNT--WARNING (set event)
IOn--Error
Off
In/Out module No. n status
IOn--Error (reset event)
IOn--Error
IOn--Error (set event)
ADMn-Error
Off
Analog/Digital module No. n
status
ADMn-Error (reset event)
ADMn-Error
ADMn-Error (set event)
INT--RTC
Off
Real Time Clock (RTC) status
INT--RTC (reset event)
INT--RTC
INT--RTC (set event)
INT--TSYNC
Off
External time synchronization
status
INT--TSYNC (reset event)
INT--TSYNC
INT--TSYNC (set event)
INT--SETCHGD
Any settings in IED changed
DRPC-CLEARED
All disturbances in Disturbance
report cleared
The events in the internal event list are time tagged with a resolution of 1ms.
This means that, when using the PC for fault tracing, it provides information on
the:
•
Module that should be changed.
•
Sequence of faults, if more than one unit is faulty.
•
Exact time when the fault occurred.
11.2.3
Diagnosing the IED status via the LHMI hint menu
GUID-7E8503E9-441B-487A-9CD7-B43463D1CAE5 v2
In order to help the user, there is an LHMI page labeled ‘Hints’. This page is
located under
Main menu/Diagnostics/IED status/Hints
. For each activated hint
there is a headline. From the headline view, an explanation page can be entered,
giving the user more information and hints about the particular topic.
Section 11
1MRK 511 425-UEN A
Troubleshooting
108
Bay control REC650 2.2 IEC
Commissioning manual
Summary of Contents for RELION REC650
Page 1: ...RELION 650 SERIES Bay control REC650 Version 2 2 Commissioning manual ...
Page 2: ......
Page 12: ...6 ...
Page 22: ...16 ...
Page 26: ...20 ...
Page 50: ...44 ...
Page 54: ...48 ...
Page 110: ...104 ...
Page 118: ...112 ...
Page 128: ...122 ...
Page 129: ...123 ...