5.1.6.1
INRPHAR Input signals
Table 510: INRPHAR Input signals
Name
Type
Default
Description
I_2H_A
SIGNAL
0
Second harmonic
phase A current
I_1H_A
SIGNAL
0
Fundamental fre-
quency phase A cur-
rent
I_2H_B
SIGNAL
0
Second harmonic
phase B current
I_1H_B
SIGNAL
0
Fundamental fre-
quency phase B cur-
rent
I_2H_C
SIGNAL
0
Second harmonic
phase C current
I_1H_C
SIGNAL
0
Fundamental fre-
quency phase C cur-
rent
BLOCK
BOOLEAN
0=False
Block input status
5.1.6.2
INRPHAR Output signals
Table 511: INRPHAR Output signals
Name
Type
Description
BLK2H
BOOLEAN
Second harmonic based
block
5.1.7
Settings
5.1.7.1
INRPHAR Group settings
Table 512: INRPHAR Group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Start value
5...100
%
1
20
Ratio of the 2.
to the 1. harmonic
leading to restraint
Operate delay time 20...60000
ms
1
20
Operate delay time
Table 513: INRPHAR Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=on
5=off
1=on
Operation Off / On
1MRS758755 C
Protection related functions
REC615 & RER615
Technical Manual
479