Delay (1) < Delay (2) < Delay (3) < Delay (4) < Delay(Def)
•
Delay (OR) < Delay (2)
When grading the operating times of several distance relays, the minimum grading time
should not be less than the sum of the circuit-breaker operating time plus 150 ms (reset time +
operating time of the measuring safety margin).
Recommended timer settings:
•
Zone 1: normally instantaneous
•
Zone 2:
Delay (2) is normally set to the sum of relay and circuit breaker operating times,
arc extinction time, signal transmission time and a tolerance margin, which amounts to
about 0.25 to 0.5 s. The tolerance includes an allowance for sequential trip-ping.
•
Zone 3:
Delay (3) is set to about 2 × Delay (2).
•
Zone 4:
Delay (4) or Delay(Def) is normally set to at least 4 × Delay (2).
Special cases may require settings, which deviate considerably from the above
recommendations.
The time steps of zones (1 to 4) must have settings less than
Delay(Def).