Signal
Description
VT-Compens
Amplitude compensation factor for the residual voltage input, enabling different
transformation ratios of the main VTs for phase and residual voltages to be
equalized.The polarity of the residual voltage can be reversed by entering
negative values.
VoltageInp
Defines the voltage input channel.
Any of the three-phase voltage inputs may be selected.Not applicable with delta
connected VTs.
SumInp
Defines the neutral voltage input channel.
Any of the single-phase voltage inputs may be selected.
Blocking
Input for blocking the function.
F: enabled
T: disabled
xx: all binary inputs (or outputs of protection functions)
Trip
Tripping signal
If the phase sequence is incorrect, tripping takes place regardless of setting (
V-
Setting).
5.15
Peak value over and undercurrent protection 50
(OCINST)
5.15.1
Mode of operation
GUID-D7DE20A4-ACBA-4383-B058-EF37A04454F0 v1
•
General current monitoring with instantaneous response (over and undercurrent)
•
Current monitoring where insensitivity to frequency is required (over and undercurrent)
5.15.2
Features
GUID-B08B6010-76E7-49F0-B403-0547FAB5381A v1
•
Processes instantaneous values and is therefore fast and largely independent of
frequency
•
Stores the peak value following pick-up
•
No suppression of DC component
•
No suppression of harmonics
•
Single or three-phase measurement
•
Maximum value detection in the three-phase mode
•
Adjustable lower frequency limit f
min
5.15.3
Inputs and outputs
5.15.3.1
CT/VT inputs
GUID-829955A0-16B4-4003-9B13-339BBA78AE46 v1
•
Current
5.15.3.2
Binary inputs
GUID-5E6D5A77-0397-4A00-A225-563A43365136 v1
•
Blocking
Section 5
1MRK 505 406-UEN B
Bay protection functions
182
Bay protection functions REB500