13.8.9.5
Setting parameters
Table 481:
LCZSPTOC (51N) Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Disabled
Enabled
-
-
Disabled
Operation Disabled/Enabled
IBase
1 - 99999
A
1
3000
Base setting for current in A
3I0 PU
1 - 2500
%IB
1
100
Zero sequence over current start value in %
of IBase
t3I0
0.000 - 60.000
s
0.001
0.000
Time delay to operate
13.8.9.6
Technical data
Table 482:
LCZSPTOC (51N)technical data
Function
Range or value
Accuracy
Operate value, zero
sequence overcurrent
(1-2500)% of IBase
± 1.0% of I
n
at I<I
n
± 1.0% of I at I>I
n
Reset ratio, zero
sequence overcurrent
>95%
-
Operate time, start
20 ms typically at 0 to 2xI
set
15 ms typically at 0 to 10xI
set
-
Reset time, start
30 ms typically at 2 to 0xI
set
-
Critical impulse time, zero
sequence overcurrent
10 ms typically at 0 to 2xI
set
2 ms typically at 0 to 10xI
set
-
Impulse margin time,
zero sequence
overcurrent
15 ms typically
-
Timer
(0.000-60.000) s
± 0.5% ± 10 ms
13.8.10
Three phase overcurrent LCP3PTOC (51)
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Three phase overcurrent
LCP3PTOC
-
51
13.8.10.1
Introduction
Three phase overcurrent (LCP3PTOC, 51) is designed for overcurrent conditions.
Section 13
1MRK505222-UUS C
Scheme communication
852
Technical reference manual
Summary of Contents for Relion 670 series
Page 1: ...Relion 670 series Line differential protection RED670 ANSI Technical reference manual...
Page 2: ......
Page 40: ...34...
Page 50: ...44...
Page 60: ...54...
Page 126: ...120...
Page 384: ...378...
Page 496: ...490...
Page 556: ...550...
Page 602: ...596...
Page 620: ...614...
Page 794: ...788...
Page 864: ...858...
Page 988: ...982...
Page 998: ...992...
Page 1084: ...1078...
Page 1164: ...1158...
Page 1168: ...1162...
Page 1220: ...1214...
Page 1230: ...1224...
Page 1231: ...1225...