12.4.4.3
Logic diagram
EXDU_BB
en04000546_ansi.vsd
VP_BB_DC
BB_DC_OP
89GREL
89GITL
BBGSOPTR
BBGSCLTR
89G_OP
89G_CL
BB_ES
AND
NOT
ANSI04000546 V1 EN
12.4.4.4
Input and output signals
Table 355:
BB_ES (3) Input signals
Name
Type
Default
Description
QC_OP
BOOLEAN
0
Busbar grounding switch 89G is in open position
QC_CL
BOOLEAN
0
Busbar grounding switch 89G is in closed position
BB_DC_OP
BOOLEAN
0
All disconnectors on this busbar part are open
VP_BB_DC
BOOLEAN
0
Status for all disconnectors on this busbar part are valid
EXDU_BB
BOOLEAN
0
No transm error from bays with disc on this busbar part
Table 356:
BB_ES (3) Output signals
Name
Type
Description
QCREL
BOOLEAN
Switching of 89G is allowed
QCITL
BOOLEAN
Switching of 89G is not allowed
BBESOPTR
BOOLEAN
89G on this busbar part is in open position
BBESCLTR
BOOLEAN
89G on this busbar part is in closed position
12.4.5
Interlocking for bus-section breaker A1A2_BS (3)
12.4.5.1
Introduction
The interlocking for bus-section breaker (A1A2_BS ,3) function is used for one bus-
section circuit breaker between section 1 and 2 according to figure
. The function
can be used for different busbars, which includes a bus-section circuit breaker.
1MRK505222-UUS C
Section 12
Control
697
Technical reference manual
Summary of Contents for Relion 670 series
Page 1: ...Relion 670 series Line differential protection RED670 ANSI Technical reference manual...
Page 2: ......
Page 40: ...34...
Page 50: ...44...
Page 60: ...54...
Page 126: ...120...
Page 384: ...378...
Page 496: ...490...
Page 556: ...550...
Page 602: ...596...
Page 620: ...614...
Page 794: ...788...
Page 864: ...858...
Page 988: ...982...
Page 998: ...992...
Page 1084: ...1078...
Page 1164: ...1158...
Page 1168: ...1162...
Page 1220: ...1214...
Page 1230: ...1224...
Page 1231: ...1225...