WA1 not grounded
WA2 not grounded
WA1 and WA2 interconn
WA1 not grounded
WA2 not grounded
WA1 and WA2 interconn
. . .
. .
Station bus
189
WA1
WA2
Bay 1
Bay n
Bus coupler
WA1 ungrounded
WA1 ungrounded
WA1 and WA2 interconn
WA1 and WA2 interconn
in other bay
289
989
189
289
989
289
189
189G
289G
en05000494_ansi.vsd
Disc 189 and 289 closed
Disc 189 and 289 closed
152
152
152
ANSI05000494 V1 EN
Figure 354:
Data exchange between interlocking modules
When invalid data such as intermediate position, loss of a control IED, or input board
error are used as conditions for the interlocking condition in a bay, a release for
execution of the function will not be given.
On the local HMI an override function exists, which can be used to bypass the
interlocking function in cases where not all the data required for the condition is valid.
For all interlocking modules these general rules apply:
•
The interlocking conditions for opening or closing of disconnectors and grounding
switches are always identical.
•
Grounding switches on the line feeder end, for example, rapid grounding switches,
are normally interlocked only with reference to the conditions in the bay where
they are located, not with reference to switches on the other side of the line. So a
line voltage indication may be included into line interlocking modules. If there is
no line voltage supervision within the bay, then the appropriate inputs must be set
to
no voltage
, and the operator must consider this when operating.
•
Grounding switches can only be operated on isolated sections for example,
without load/voltage. Circuit breaker contacts cannot be used to isolate a section,
that is, the status of the circuit breaker is irrelevant as far as the grounding switch
operation is concerned.
•
Disconnectors cannot break power current or connect different voltage systems.
Disconnectors in series with a circuit breaker can only be operated if the circuit
breaker is open, or if the disconnectors operate in parallel with other closed
connections. Other disconnectors can be operated if one side is completely
1MRK505222-UUS C
Section 12
Control
693
Technical reference manual
Summary of Contents for Relion 670 series
Page 1: ...Relion 670 series Line differential protection RED670 ANSI Technical reference manual...
Page 2: ......
Page 40: ...34...
Page 50: ...44...
Page 60: ...54...
Page 126: ...120...
Page 384: ...378...
Page 496: ...490...
Page 556: ...550...
Page 602: ...596...
Page 620: ...614...
Page 794: ...788...
Page 864: ...858...
Page 988: ...982...
Page 998: ...992...
Page 1084: ...1078...
Page 1164: ...1158...
Page 1168: ...1162...
Page 1220: ...1214...
Page 1230: ...1224...
Page 1231: ...1225...