12.3.10.4
Input and output signals
Table 347:
RESIN1 Input signals
Name
Type
Default
Description
BAY_ACK
BOOLEAN
0
Another bay has acknowledged the reservation
request from this bay
BAY_VAL
BOOLEAN
0
The reservervation and acknowledge signals from
another bay are valid
BAY_RES
BOOLEAN
0
Request from other bay to reserve this bay
Table 348:
RESIN1 Output signals
Name
Type
Description
ACK_F_B
BOOLEAN
All other bays have acknowledged the reservation
request from this bay
ANY_ACK
BOOLEAN
Any other bay has acknowledged the reservation
request from this bay
VALID_TX
BOOLEAN
The reservation and acknowledge signals from other
bays are valid
RE_RQ_B
BOOLEAN
Request from other bay to reserve this bay
V_RE_RQ
BOOLEAN
Check if the request of reserving this bay is valid
EXCH_OUT
INTEGER
Used for exchange signals between different ResIn
blocks
Table 349:
RESIN2 Input signals
Name
Type
Default
Description
EXCH_IN
INTEGER
5
Used for exchange signals between different ResIn
blocks
BAY_ACK
BOOLEAN
0
Another bay has acknowledged the reservation
request from this bay
BAY_VAL
BOOLEAN
0
The reservervation and acknowledge signals from
another bay are valid
BAY_RES
BOOLEAN
0
Request from other bay to reserve this bay
1MRK505222-UUS C
Section 12
Control
689
Technical reference manual
Summary of Contents for Relion 670 series
Page 1: ...Relion 670 series Line differential protection RED670 ANSI Technical reference manual...
Page 2: ......
Page 40: ...34...
Page 50: ...44...
Page 60: ...54...
Page 126: ...120...
Page 384: ...378...
Page 496: ...490...
Page 556: ...550...
Page 602: ...596...
Page 620: ...614...
Page 794: ...788...
Page 864: ...858...
Page 988: ...982...
Page 998: ...992...
Page 1084: ...1078...
Page 1164: ...1158...
Page 1168: ...1162...
Page 1220: ...1214...
Page 1230: ...1224...
Page 1231: ...1225...