Figure 307:
Simplified logic diagram for fuse failure supervision function, Main logic
11.2.3
Function block
ANSI05000700-2-en.vsd
SDDRFUF
I3P*
V3P*
BLOCK
52A
MCBOP
89B
BLKTRIP
BLKZ
BLKV
3PH
DLD1PH
DLD3PH
ANSI05000700 V2 EN
Figure 308:
SDDRFUF function block
11.2.4
Input and output signals
Table 311:
SDDRFUF Input signals
Name
Type
Default
Description
I3P
GROUP
SIGNAL
-
Current connection
V3P
GROUP
SIGNAL
-
Voltage connection
BLOCK
BOOLEAN
0
Block of function
52a
BOOLEAN
0
Active when circuit breaker is closed
MCBOP
BOOLEAN
0
Active when external Miniature Circuit Breaker opens
protected voltage circuit
89b
BOOLEAN
0
Active when line disconnect switch is open
BLKTRIP
BOOLEAN
0
Blocks operation of function when active
Table 312:
SDDRFUF Output signals
Name
Type
Description
BLKZ
BOOLEAN
Start of current and voltage controlled function
BLKV
BOOLEAN
General pickup
3PH
BOOLEAN
Three-phase pickup
DLD1PH
BOOLEAN
Dead line condition in at least one phase
DLD3PH
BOOLEAN
Dead line condition in all three phases
1MRK505222-UUS C
Section 11
Secondary system supervision
611
Technical reference manual
Summary of Contents for Relion 670 series
Page 1: ...Relion 670 series Line differential protection RED670 ANSI Technical reference manual...
Page 2: ......
Page 40: ...34...
Page 50: ...44...
Page 60: ...54...
Page 126: ...120...
Page 384: ...378...
Page 496: ...490...
Page 556: ...550...
Page 602: ...596...
Page 620: ...614...
Page 794: ...788...
Page 864: ...858...
Page 988: ...982...
Page 998: ...992...