Table 245:
GOPPDOP (32) Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
IBase
1 - 99999
A
1
3000
Base setting for current level
VBase
0.05 - 2000.00
kV
0.05
400.00
Base setting for voltage level
Mode
A, B, C
Arone
Pos Seq
AB
BC
CA
A
B
C
-
-
Pos Seq
Selection of measured current and voltage
7.12.6
Technical data
Table 246:
GOPPDOP (32) technical data
Function
Range or value
Accuracy
Power level
(0.0–500.0)% of S
base
At low setting:
(0.5-2.0)% of S
base
(2.0-10)% of S
base
± 1.0% of S
r
at S < S
r
± 1.0% of S at S > S
r
<
±
50% of set value
<
±
20% of set value
Characteristic angle
(-180.0–180.0) degrees
2 degrees
Timers
(0.00-6000.00) s
± 0.5% ± 10 ms
7.13
Broken conductor check BRCPTOC (46)
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Broken conductor check
BRCPTOC
-
46
7.13.1
Introduction
Conventional protection functions can not detect the broken conductor condition.
Broken conductor check (BRCPTOC, 46) function, consisting of continuous current
unsymmetrical check on the line where the IED is connected will give alarm or trip at
detecting broken conductors.
Section 7
1MRK505222-UUS C
Current protection
486
Technical reference manual
Summary of Contents for Relion 670 series
Page 1: ...Relion 670 series Line differential protection RED670 ANSI Technical reference manual...
Page 2: ......
Page 40: ...34...
Page 50: ...44...
Page 60: ...54...
Page 126: ...120...
Page 384: ...378...
Page 496: ...490...
Page 556: ...550...
Page 602: ...596...
Page 620: ...614...
Page 794: ...788...
Page 864: ...858...
Page 988: ...982...
Page 998: ...992...
Page 1084: ...1078...
Page 1164: ...1158...
Page 1168: ...1162...
Page 1220: ...1214...
Page 1230: ...1224...
Page 1231: ...1225...