Table 238:
GUPPDUP (37) Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
IBase
1 - 99999
A
1
3000
Base setting for current level
VBase
0.05 - 2000.00
kV
0.05
400.00
Base setting for voltage level
Mode
A, B, C
Arone
Pos Seq
AB
BC
CA
A
B
C
-
-
Pos Seq
Selection of measured current and voltage
7.11.6
Technical data
Table 239:
GUPPDUP (37) technical data
Function
Range or value
Accuracy
Power level
(0.0–500.0)% of
SBase
At low setting:
(0.5-2.0)% of
SBase
(2.0-10)% of
SBase
± 1.0% of S
r
at S < S
r
± 1.0% of S at S > S
r
< ± 50% of set value
< ± 20% of set value
Characteristic angle
(-180.0–180.0) degrees
2 degrees
Timers
(0.00-6000.00) s
± 0.5% ± 10 ms
7.12
Directional overpower protection GOPPDOP (32)
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Directional overpower protection
GOPPDOP
P >
DOCUMENT172362-IMG158942
V1 EN
32
7.12.1
Introduction
The task of a generator in a power plant is to convert mechanical energy available as a
torque on a rotating shaft to electric energy.
Section 7
1MRK505222-UUS C
Current protection
478
Technical reference manual
Summary of Contents for Relion 670 series
Page 1: ...Relion 670 series Line differential protection RED670 ANSI Technical reference manual...
Page 2: ......
Page 40: ...34...
Page 50: ...44...
Page 60: ...54...
Page 126: ...120...
Page 384: ...378...
Page 496: ...490...
Page 556: ...550...
Page 602: ...596...
Page 620: ...614...
Page 794: ...788...
Page 864: ...858...
Page 988: ...982...
Page 998: ...992...
Page 1084: ...1078...
Page 1164: ...1158...
Page 1168: ...1162...
Page 1220: ...1214...
Page 1230: ...1224...
Page 1231: ...1225...