7.6.2
Principle of operation
7.6.2.1
Function inputs
The function is using phasors of the residual current and voltage. Group signals I3P
and V3P containing phasors of residual current and voltage is taken from pre-processor
blocks.
The sensitive directional ground fault protection has the following sub-functions
included:
Directional residual current protection measuring 3I
0
·cos φ
φ is defined as the angle between the residual current 3I
0
and the reference voltage.
Vref = -3V
0
e
jRCADir
, that is -3V
0
rotated by the set characteristic angle
RCADir
(φ=ang(3I
0
)-ang(V
ref
) ).
RCADir
is normally set equal to 0 in a high impedance
grounded network with a neutral point resistor as the active current component is
appearing out on the faulted feeder only.
RCADir
is set equal to -90° in an isolated
network as all currents are mainly capacitive. The function operates when 3I
0
·cos φ
gets larger than the set value.
-3V
0
=V
ref
3I
0
RCA = 0
°,
ROA = 90
°
= ang(3I
0
) - ang(3V
ref
)
3I
0
cos
en06000648_ansi.vsd
V
ref
ANSI06000648 V1 EN
Figure 218:
RCADir set to 0°
Section 7
1MRK505222-UUS C
Current protection
438
Technical reference manual
Summary of Contents for Relion 670 series
Page 1: ...Relion 670 series Line differential protection RED670 ANSI Technical reference manual...
Page 2: ......
Page 40: ...34...
Page 50: ...44...
Page 60: ...54...
Page 126: ...120...
Page 384: ...378...
Page 496: ...490...
Page 556: ...550...
Page 602: ...596...
Page 620: ...614...
Page 794: ...788...
Page 864: ...858...
Page 988: ...982...
Page 998: ...992...
Page 1084: ...1078...
Page 1164: ...1158...
Page 1168: ...1162...
Page 1220: ...1214...
Page 1230: ...1224...
Page 1231: ...1225...