Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Distance protection zone, quadrilateral
characteristic, separate settings (zone
1)
ZMRPDIS
S00346 V1 EN
21
Distance protection zone, quadrilateral
characteristic, separate settings (zone
2-5)
ZMRAPDIS
S00346 V1 EN
21
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Directional impedance quadrilateral
ZDRDIR
Z<->
21D
6.9.1
Introduction
The line distance protection is up to five zone full scheme protection with three fault
loops for phase-to-phase faults and three fault loops for phase-to-ground fault for each
of the independent zones. Individual settings for each zone in resistive and reactive
reach gives flexibility for use as back-up protection for transformer connected to
overhead lines and cables of different types and lengths.
Mho alternative quadrilateral characteristic is available.
ZMRPDIS (21) together with Phase selection, quadrilateral characteristic with settable
angle FRPSPDIS (21) has functionality for load encroachment, which increases the
possibility to detect high resistive faults on heavily loaded lines, as shown in figure
Section 6
1MRK505222-UUS C
Impedance protection
304
Technical reference manual
Summary of Contents for Relion 670 series
Page 1: ...Relion 670 series Line differential protection RED670 ANSI Technical reference manual...
Page 2: ......
Page 40: ...34...
Page 50: ...44...
Page 60: ...54...
Page 126: ...120...
Page 384: ...378...
Page 496: ...490...
Page 556: ...550...
Page 602: ...596...
Page 620: ...614...
Page 794: ...788...
Page 864: ...858...
Page 988: ...982...
Page 998: ...992...
Page 1084: ...1078...
Page 1164: ...1158...
Page 1168: ...1162...
Page 1220: ...1214...
Page 1230: ...1224...
Page 1231: ...1225...