Name
Type
Default
Description
IN8
BOOLEAN
0
Input 8
IN9
BOOLEAN
0
Input 9
IN10
BOOLEAN
0
Input 10
IN11
BOOLEAN
0
Input 11
IN12
BOOLEAN
0
Input 12
IN13
BOOLEAN
0
Input 13
IN14
BOOLEAN
0
Input 14
IN15
BOOLEAN
0
Input 15
IN16
BOOLEAN
0
Input 16
PID-6944-OUTPUTSIGNALS v2
Table 692: BTIGAPC Output signals
Name
Type
Description
OUT
INTEGER
Output value
15.11.5
Settings
ABBD8E283673 v3
The function does not have any parameters available in the local HMI or PCM600.
15.11.6
Monitored data
PID-6944-MONITOREDDATA v2
Table 693: BTIGAPC Monitored data
Name
Type
Values (Range)
Unit
Description
OUT
INTEGER
-
-
Output value
15.11.7
Operation principle
SEMOD158425-4 v6
The Boolean 16 to integer conversion with logic node representation function (BTIGAPC) will
transfer a combination of up to 16 binary inputs INx, where 1≤x≤16, to an integer. Each INx
represents a value according to the table below from 0 to 32768. This follows the general formula:
INx = 2
x-1
where 1≤x≤16. The sum of all the values on the activated INx will be available on the
output OUT as a sum of the integer values of all the inputs INx that are activated. OUT is an
integer. When all INx (where 1≤x≤16) are activated, that is = Boolean 1, it corresponds to that
integer 65535 is available on the output OUT. If the BLOCK input is activated, it will freeze the
logical outputs at the last value.
Values of each of the different OUTx from function block BTIGAPC for 1≤x≤16.
The sum of the value on each INx corresponds to the integer presented on the output OUT on the
function block BTIGAPC.
Section 15
1MRK 502 066-UUS B
Logic
988
Technical manual
Summary of Contents for Relion 670 series
Page 1: ... RELION 670 SERIES Generator protection REG670 Version 2 1 ANSI Technical manual ...
Page 2: ......
Page 48: ...42 ...
Page 62: ...56 ...
Page 182: ...176 ...
Page 692: ...686 ...
Page 726: ...720 ...
Page 1014: ...1008 ...
Page 1242: ...1236 ...
Page 1362: ...1356 ...
Page 1386: ...1380 ...
Page 1422: ...1416 ...
Page 1431: ...1425 ...