Vpickup
VBase kV
>
⋅
(%)
(
) / 3
EQUATION1610 V2 EN-US
(Equation 174)
and operation for phase-to-phase voltage over:
Vpickup
(%) VBase(kV)
>
×
EQUATION1992 V1 EN-US
(Equation 175)
When phase-to-ground voltage measurement is selected the function
automatically introduces division of the base value by the square root of three.
9.2.7.1
Measurement principle
M15330-6 v6
All the three voltages are measured continuously, and compared with the set values,
Pickup1 for
Step 1 and
Pickup2 for Step 2. The parameters OpMode1 and OpMode2 influence the requirements
to activate the PICKUP outputs. Either
1 out of 3, 2 out of 3 or 3 out of 3 measured voltages have to
be higher than the corresponding set point to issue the corresponding PICKUP signal.
To avoid oscillations of the output PICKUP signal, a hysteresis is included.
9.2.7.2
Time delay
M15330-10 v9
The time delay for the two steps can be either definite time delay (DT) or inverse time delay (TOV).
For the inverse time delay four different modes are available:
•
inverse curve A
•
inverse curve B
•
inverse curve C
•
customer programmable inverse curve
The type A curve is described as:
t
TD
V
Vpickup
Vpickup
=
−
>
>
EQUATION1625 V2 EN-US
(Equation 176)
where:
Vpickup>
Set value for step 1 and step 2
V
Measured voltage
The type B curve is described as:
1MRK 502 066-UUS B
Section 9
Voltage protection
617
Technical manual
Summary of Contents for Relion 670 series
Page 1: ... RELION 670 SERIES Generator protection REG670 Version 2 1 ANSI Technical manual ...
Page 2: ......
Page 48: ...42 ...
Page 62: ...56 ...
Page 182: ...176 ...
Page 692: ...686 ...
Page 726: ...720 ...
Page 1014: ...1008 ...
Page 1242: ...1236 ...
Page 1362: ...1356 ...
Page 1386: ...1380 ...
Page 1422: ...1416 ...
Page 1431: ...1425 ...