Table 337: UV2PTUV (27) Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
ConnType
PhN DFT
PhPh RMS
PhN RMS
PhPh DFT
-
-
PhN DFT
Group selector for connection type
GlobalBaseSel
1 - 12
-
1
1
Selection of one of the Global Base Value
groups
9.1.6
Monitored data
PID-3586-MONITOREDDATA v5
Table 338: UV2PTUV (27) Monitored data
Name
Type
Values (Range)
Unit
Description
VA
REAL
-
kV
Voltage in phase A
VB
REAL
-
kV
Voltage in phase B
VC
REAL
-
kV
Voltage in phase C
9.1.7
Operation principle
M15326-3 v8
Two-step undervoltage protection (UV2PTUV ,27) is used to detect low power system voltage.
UV2PTUV (27) has two voltage measuring steps with separate time delays. If one, two or three
phase voltages decrease below the set value, a corresponding PICKUP signal is generated.
UV2PTUV (27) can be set to PICKUP/TRIP based on
1 out of 3, 2 out of 3 or 3 out of 3 of the
measured voltages, being below the set point. If the voltage remains below the set value for a time
period corresponding to the chosen time delay, the corresponding trip signal is issued. To avoid
an unwanted trip due to disconnection of the related high voltage equipment, a voltage controlled
blocking of the function is available, that is, if the voltage is lower than the set blocking level the
function is blocked and no PICKUP or TRIP signal is generated.The time delay characteristic is
individually chosen for each step and can be either definite time delay or inverse time delay.
UV2PTUV (27) can be set to measure phase-to-ground fundamental value, phase-to-phase
fundamental value, phase-to-ground true RMS value or phase-to-phase true RMS value. The choice
of the measuring is done by the parameter
ConnType. The voltage related settings are made in
percent of base voltage which is set in kV phase-to-phase voltage. This means operation for
phase-to-ground voltage under:
(%)
(
)
3
Vpickup
VBase kV
<
×
EQUATION1606 V1 EN-US
(Equation 168)
and operation for phase-to-phase voltage under:
Vpickup
(%) VBase(kV)
<
×
EQUATION1991-ANSI V1 EN-US
(Equation 169)
1MRK 502 066-UUS B
Section 9
Voltage protection
603
Technical manual
Summary of Contents for Relion 670 series
Page 1: ... RELION 670 SERIES Generator protection REG670 Version 2 1 ANSI Technical manual ...
Page 2: ......
Page 48: ...42 ...
Page 62: ...56 ...
Page 182: ...176 ...
Page 692: ...686 ...
Page 726: ...720 ...
Page 1014: ...1008 ...
Page 1242: ...1236 ...
Page 1362: ...1356 ...
Page 1386: ...1380 ...
Page 1422: ...1416 ...
Page 1431: ...1425 ...