![ABB Relion 670 series Technical Manual Download Page 504](http://html.mh-extra.com/html/abb/relion-670-series/relion-670-series_technical-manual_3045226504.webp)
Name
Values (Range)
Unit
Step
Default
Description
tPRCrv4
0.005 - 3.000
-
0.001
0.500
Param PR for customized inverse reset
time curve for step 4
tTRCrv4
0.005 - 100.000
-
0.001
13.500
Param TR for customized inverse reset
time curve for step 4
tCRCrv4
0.1 - 10.0
-
0.1
1.0
Param CR for customized inverse reset
time curve for step 4
Table 239: NS4PTOC (46I2) Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
GlobalBaseSel
1 - 12
-
1
1
Selection of one of the Global Base Value
groups
8.5.6
Monitored data
PID-6530-MONITOREDDATA v3
Table 240: NS4PTOC (46I2) Monitored data
Name
Type
Values (Range)
Unit
Description
IOp
REAL
-
A
Operating current level
VPol
REAL
-
kV
Polarizing voltage level
VPOLIANG
REAL
-
deg
Polarizing angle between voltage and
current
8.5.7
Operation principle
GUID-8923EC0B-A5BA-431B-9699-EB67E2637560 v3
Four step negative sequence overcurrent protection NS4PTOC (4612) function has the following
three “Analog Inputs” on its function block in the configuration tool:
1.
I3P, input used for “Operating Quantity”.
2.
V3P, input used for “Polarizing Quantity”.
3.
I3PDIR, input used for "Directional finding"
These inputs are connected from the corresponding pre-processing function blocks in the
Configuration Tool within PCM600.
8.5.7.1
Operating quantity within the function
GUID-8F0A5BDE-AC98-4188-9085-42A8DF00C476 v3
Four step negative sequence overcurrent protection NS4PTOC (46I2) function always uses
negative sequence current (I2) for its operating quantity. The negative sequence current is
calculated from three-phase current input within the IED. The pre-processing block calculates I2
from the first three inputs into the pre-processing block by using the following formula:
(
)
2
1
2
3
I
IA a IB a IC
= ×
+
×
+ ×
ANSIEQUATION2266 V1 EN-US
(Equation 132)
Section 8
1MRK 502 066-UUS B
Current protection
498
Technical manual
Summary of Contents for Relion 670 series
Page 1: ... RELION 670 SERIES Generator protection REG670 Version 2 1 ANSI Technical manual ...
Page 2: ......
Page 48: ...42 ...
Page 62: ...56 ...
Page 182: ...176 ...
Page 692: ...686 ...
Page 726: ...720 ...
Page 1014: ...1008 ...
Page 1242: ...1236 ...
Page 1362: ...1356 ...
Page 1386: ...1380 ...
Page 1422: ...1416 ...
Page 1431: ...1425 ...