Indicates to the IED that the injection on X82 is blocked. The reason for blocking is indicated
in the REX060 LCD.
•
SAT_NO on X81 pin 6:
Indicates to the IED that there is a risk of saturated amplifier on voltage and/or current
output at X81, indication is also given in the REX060 LCD.
•
COMMON on X81 terminal 7:
Common return for X81 terminal 5 and 6
Power status
•
X11 terminal 3:
Fail, power off NC
•
X11 terminal 1:
Ready, power off NO
•
X11 terminal 2:
Common
23.3
Coupling capacitor unit REX061
23.3.1
Introduction
GUID-39A03C0F-44DC-47DD-9D7E-66C8292CD3A8 v1
REX061 isolates the injection circuit from the rotor exciter voltage.
The REX061 coupling capacitor unit grounding point and grounding brush of the rotor shaft
should be properly interconnected.
23.3.2
Design
GUID-F7DCDF09-CB35-4C6C-8623-4285BDB39E15 v1
Measure points are added to the capacitor box that enables the measuring of rotor voltages
without any connection to a hazardous voltage, by the use of protective impedance. This enables
the usage of standard oscilloscope or handheld DVM.
The measure ports cause an additional rotor impedance of 20 MΩ per terminal to
ground. However, the rotor calibration procedure extracts this impedance.
1MRK 502 066-UUS B
Section 23
Injection equipment hardware
1365
Technical manual
Summary of Contents for Relion 670 series
Page 1: ... RELION 670 SERIES Generator protection REG670 Version 2 1 ANSI Technical manual ...
Page 2: ......
Page 48: ...42 ...
Page 62: ...56 ...
Page 182: ...176 ...
Page 692: ...686 ...
Page 726: ...720 ...
Page 1014: ...1008 ...
Page 1242: ...1236 ...
Page 1362: ...1356 ...
Page 1386: ...1380 ...
Page 1422: ...1416 ...
Page 1431: ...1425 ...