I/O
100k
W
100nF
Soft ground
en07000242.vsd
IEC07000242 V1 EN-US
Figure 667: Schematic view of soft ground
Grounding
At special problems with ground loops, the soft ground connection for the IIO-ground can be
tested.
Three different kinds of grounding principles can be set (used for fault tracing):
1.
Direct ground - The normal grounding is direct ground, connect terminal 2 directly to the
chassis.
2.
No ground - Leave the connector without any connection.
3.
Soft ground - Connect soft ground pin (3), see figure
X.21 connector
Table 1041:Pinout for the X.21 communication connector
Pin number
Signal
1
Shield (ground)
2
TXD A
3
Control A
4
RXD A
6
Signal timing A
8
Ground
9
TXD B
10
Control B
11
RXD B
13
Signal timing B
5,7,12,14,15
Not used
22.2.16.3
Functionality
GUID-4512904E-08D1-47EC-B005-E66170CEB130 v1
The data format is HDLC. The speed for the transmission of the messages used is 64 kbit/s.
Section 22
1MRK 502 066-UUS B
IED hardware
1328
Technical manual