background image

DO name

DO type

DA name

FC

T

Signal

Mon/C

md

Description

OpnCT

v1_dSPS

stVal

ST

-

OPENCT

Mon

An open CT was detected

q

ST

-

OPENCT

Mon

Quality: An open CT was detected

t

ST

-

OPENCT

Mon

Timestamp: An open CT was

detected

OpnCTAlm

v1_dSPS

stVal

ST

-

OPENCTAL

Mon

Open CT Alarm output signal.

Issued after a delay ...

q

ST

-

OPENCTAL

Mon

Quality: Open CT Alarm output

signal. Issued after a delay ...

t

ST

-

OPENCTAL

Mon

Timestamp: Open CT Alarm

output signal. Issued after a

delay ...

7.5.1.9 

Line differential protection, 6 CT sets, 35 line ends L6CPDIF

LN type

LN prefix LN class Function block name

L6CPDIF (revision 2) L6C

PDIF

L6CPDIF

Table 19:

L6CPDIF Logical node data

DO name

DO type

DA name

FC

T

Signal

Mon/C

md

Description

Str

a_dACD

general

ST

-

START

Mon

Common, main, start output signal

phsA

ST

-

STL1

Mon

Start signal from phase L1

phsB

ST

-

STL2

Mon

Start signal from phase L2

phsC

ST

-

STL3

Mon

Start signal from phase L3

q

ST

-

START

Mon

Quality: Common, main, start

output signal

t

ST

-

START

Mon

Timestamp: Common, main, start

output signal

Op

a_dACT

general

ST

T

TRIP

Mon

Common, main, trip output signal

phsA

ST

T

TRL1

Mon

Trip signal from phase L1

phsB

ST

T

TRL2

Mon

Trip signal from phase L2

phsC

ST

T

TRL3

Mon

Trip signal from phase L3

q

ST

T

TRIP

Mon

Quality: Common, main, trip

output signal

t

ST

T

TRIP

Mon

Timestamp: Common, main, trip

output signal

Mod

a_dINC

Oper.ctlVal

CO

-

Mod

Cmd

Mode parameter for 61850

Oper.origin.orCat

CO

-

Mod

Cmd

Mode parameter for 61850

Oper.origin.orIdent

CO

-

Mod

Cmd

Mode parameter for 61850

Oper.ctlNum

CO

-

Mod

Cmd

Mode parameter for 61850

Oper.T

CO

-

Mod

Cmd

Mode parameter for 61850

Table continues on next page

1MRK 511 349-UEN -

Section 7

Logical node data model

670 series 2.1 IEC

103

Communication protocol manual

Summary of Contents for Relion 670 series

Page 1: ...Relion Protection and Control 670 series 2 1 IEC IEC 61850 Edition 1 Communication protocol manual...

Page 2: ......

Page 3: ...Document ID 1MRK 511 349 UEN Issued December 2015 Revision Product version 2 1 Copyright 2015 ABB All rights reserved...

Page 4: ...rms of such license This product includes software developed by the OpenSSL Project for use in the OpenSSL Toolkit http www openssl org This product includes cryptographic software written developed b...

Page 5: ...roduct failure would create a risk for harm to property or persons including but not limited to personal injuries or death shall be the sole responsibility of the person or entity applying the equipme...

Page 6: ...d concerning electrical equipment for use within specified voltage limits Low voltage directive 2006 95 EC This conformity is the result of tests conducted by ABB in accordance with the product standa...

Page 7: ...n 28 The IED section 29 Tool concept 32 Engineering concept in IEC 61850 6 33 Section 4 Communication profile 35 Section 5 Supported services 37 Section 6 Data sets and control blocks 41 Data sets 41...

Page 8: ...r differential protection 2 zones three phase BCZTPDIF 99 Busbar differential protection 2 zones single phase BCZSPDIF 99 Line differential protection 3 CT sets 23 line ends L3CPDIF 100 Line different...

Page 9: ...ZGVPDIS 146 Directional overpower PDOP 149 Directional over power protection GOPPDOP 149 Directional underpower PDUP 150 Rate of change of frequency PFRC 152 Rate of change frequency protection SAPFRC...

Page 10: ...ction NS4PTOC 188 Four step phase overcurrent protection OC4PTOC 193 Four step single phase overcurrent protection PH4SPTOC 197 Four step residual overcurrent protection EF4PTOC 201 Sudden change in c...

Page 11: ...Radial feeder protection PAPGAPC 254 Out of step protection PPAM 256 Out of step protection OOSPPAM 256 PoleSlip Out of step protection PSPPPAM 257 Earth fault protection PHIZ 259 ROTIPHIZ 64R 259 10...

Page 12: ...n DPGAPC 292 Single point generic control 8 signals SPC8GAPC 293 Event counter with limit supervision L4UFCNT 296 IEC61850 generic communication I O functions SPGGIO 297 IEC61850 generic communication...

Page 13: ...inputs TCLYLTC 337 Section 8 GOOSE receive blocks 341 Interlock receive INTLKRCV 341 Horizontal communication via GOOSE for interlocking GOOSEINTLKRCV 341 Binary Receive BINRCV 342 Goose binary receiv...

Page 14: ...Section 10 Glossary 351 Glossary 351 Table of contents 8 670 series 2 1 IEC Communication protocol manual...

Page 15: ...the communication system engineer or system integrator responsible for pre engineering and engineering for communication setup in a substation from an IED perspective The system engineer or system int...

Page 16: ...IEDs to the project structure The manual also recommends a sequence for the engineering of protection and control functions LHMI functions as well as communication engineering for IEC 60870 5 103 IEC...

Page 17: ...n be used as a technical reference during the engineering phase installation and commissioning phase and during normal service The communication protocol manual describes the communication protocols s...

Page 18: ...manual 1MRK 502 065 UEN Commissioning manual 1MRK 502 067 UEN Product guide 1MRK 502 068 BEN Technical manual 1MRK 502 066 UEN Type test certificate 1MRK 502 068 TEN Documents related to REL670 Docume...

Page 19: ...n 2 1MRK 511 350 UEN Communication protocol manual LON 1MRK 511 352 UEN Communication protocol manual SPA 1MRK 511 353 UEN Point list manual DNP3 1MRK 511 354 UUS Accessories guide 1MRK 514 012 BEN Cy...

Page 20: ...finitions of important terms Push button navigation in the LHMI menu structure is presented by using the push button icons For example to navigate between the options use and HMI menu paths are presen...

Page 21: ...GGAPC AEGPVOC AGSAL AGSAL SECLLN0 AGSAL ALMCALH ALMCALH ALMCALH ALTIM ALTIM ALTMS ALTMS ALTRK ALTRK BCZSPDIF BCZSPDIF BCZSPDIF BCZTPDIF BCZTPDIF BCZTPDIF BDCGAPC SWSGGIO BBCSWI BDCGAPC BRCPTOC BRCPTOC...

Page 22: ..._B5 BUTPTRC BUTPTRC BUTPTRC_B6 BUTPTRC BUTPTRC BUTPTRC_B7 BUTPTRC BUTPTRC BUTPTRC_B8 BUTPTRC BUTPTRC BZISGGIO BZISGGIO BZISGAPC BZITGGIO BZITGGIO BZITGAPC BZNSPDIF_A BZNSPDIF BZASGAPC BZASPDIF BZNSGAP...

Page 23: ...PGAPC DRPRDRE DRPRDRE DRPRDRE ECPSCH ECPSCH ECPSCH ECRWPSCH ECRWPSCH ECRWPSCH EF2PTOC EF2LLN0 EF2PTRC EF2RDIR GEN2PHAR PH1PTOC EF2PTRC EF2RDIR GEN2PHAR PH1PTOC EF4PTOC EF4LLN0 EF4PTRC EF4RDIR GEN4PHAR...

Page 24: ...T L4UFCNT L4UFCNT L6CPDIF L6CPDIF L6CGAPC L6CPDIF L6CPHAR L6CPTRC LAPPGAPC LAPPLLN0 LAPPPDUP LAPPPUPF LAPPPDUP LAPPPUPF LCCRPTRC LCCRPTRC LCCRPTRC LCNSPTOC LCNSPTOC LCNSPTOC LCNSPTOV LCNSPTOV LCNSPTOV...

Page 25: ...C4LLN0 GEN4PHAR PH3PTOC PH3PTRC GEN4PHAR PH3PTOC PH3PTRC OEXPVPH OEXPVPH OEXPVPH OOSPPAM OOSPPAM OOSPPAM OOSPTRC OV2PTOV GEN2LLN0 OV2PTOV PH1PTRC OV2PTOV PH1PTRC PAPGAPC PAPGAPC PAPGAPC PCFCNT PCGGIO...

Page 26: ...SMBRREC SMBRREC SMBRREC SMPPTRC SMPPTRC SMPPTRC SP16GAPC SP16GGIO SP16GAPC SPC8GAPC SPC8GGIO SPC8GAPC SPGAPC SPGGIO SPGAPC SSCBR SSCBR SSCBR SSIMG SSIMG SSIMG SSIML SSIML SSIML STBPTOC STBPTOC BBPMSS...

Page 27: ...C PH1PTRC PH1PTUV VRPVOC VSGAPC VSGGIO VSGAPC WRNCALH WRNCALH WRNCALH ZC1PPSCH ZPCPSCH ZPCPSCH ZC1WPSCH ZPCWPSCH ZPCWPSCH ZCLCPSCH ZCLCPLAL ZCLCPSCH ZCPSCH ZCPSCH ZCPSCH ZCRWPSCH ZCRWPSCH ZCRWPSCH ZCV...

Page 28: ...MAPDIS ZMMAPDIS ZMMPDIS ZMMPDIS ZMMPDIS ZMQAPDIS ZMQAPDIS ZMQAPDIS ZMQPDIS ZMQPDIS ZMQPDIS ZMRAPDIS ZMRAPDIS ZMRAPDIS ZMRPDIS ZMRPDIS ZMRPDIS ZMRPSB ZMRPSB ZMRPSB ZSMGAPC ZSMGAPC ZSMGAPC Section 1 1MR...

Page 29: ...dard is applied in the IEDs References and brief descriptions of the standard are also included It is assumed that the reader has basic knowledge of the IEC 61850 standard The following parts of the I...

Page 30: ...ple a transformer differential or line differential protection because the standard defines only a differential protection Therefore it is possible to adapt the logical node which is defined in the st...

Page 31: ...ation structure for substations and feeder equipment Common data classes IEC 61850 7 4 First edition 2003 05 Ref number IEC 61850 7 4 2003 E Communication networks and systems in substations Part 7 4...

Page 32: ...26...

Page 33: ...and enums The system structure is defined by the organization of the plant structure in PCM600 The signal engineering and the signal routing are IET600 tasks signal engineering regarding DS rcb gcb GO...

Page 34: ...nd or in the communication structure All needed logical nodes of an IED are linked to the substation section by the SCL tool A reference to GOOSE Control Blocks GoCB is included in the communication s...

Page 35: ...Access Point AP Address GSE GoCBs Communication AP IED server Access Point AP Address GSE GoCBs Communication IED server Access Point AP Address GSE GoCBs Communication AP IED client Access Point AP A...

Page 36: ...nitoring direction and sender of commands control These logical nodes have no data objects They are only used to link the report control blocks BRCBs from the server IEDs They have to read their infor...

Page 37: ...ssages In the IED series the data sets and the control blocks shall be located to LD0 The LN LPHD is a special logical node per LD and contains data objects that describe the status of the physical de...

Page 38: ...except for the receiving of GOOSE information that has a dependency with the system tool IEC 61850 engineering with PCM600 PCM600 IEC61850 Configuration tool and IET600 PCM600 When an IED is instanti...

Page 39: ...cross reference the signals in SMT Import the SCD file to PCM600 to receive GOOSE data For each IED that shall receive GOOSE information the received data is connected to the applications using SMT in...

Page 40: ...the idea is that the IED tool provides the CID or ICD file for each IED These ICD CID files are then imported into the system tool and merged into a SCD file representing the complete substation or a...

Page 41: ...cation network has to take these two specifications and adapt their respective product to the requirements and definitions given in the standard To make this profile visible to all other partners so t...

Page 42: ...0153 1 en vsd IEC09000153 V1 EN Figure 7 Overview of functionality and profiles according to IEC 61850 8 1 Out of this content the implementation supports GOOSE TimeSync using SNTP The peer to peer ve...

Page 43: ...e0 Logical Node 0 Change or edit of setting values as well as reading of setting values is neither supported nor visible in IEC 61850 edition 1 The Setting range is expressed in the minVal and maxVal...

Page 44: ...en vsd IEC15000002 V1 EN Figure 8 Enabling parameter setting via IEC 61850 Setting parameter values over the communication link doesn t require any authorization if Enable61850Setting has been set to...

Page 45: ...ubstation event GOOSE The structured GOOSE is supported This means that the data sets can be defined with FCDA as well as explicit attributes The supported data types to be published and received over...

Page 46: ...ment VMSQI Voltage sequence measurement VNMMXU Phase neutral voltage measurement MVGAPC IEC 61850 generic communication I O functions Generic function blocks are provided to make available to the 6185...

Page 47: ...rent ACT configuration The default data sets can be modified or removed in the engineering tools No RCBs are created automatically by PCM600 However the configured IEDs are delivered with RCBs for all...

Page 48: ...while the unbuffered is sent upon data change and not stored during interruption The content of a BRCB is listed in IEC 61850 7 2 in clause 14 The BRCB contains many attributes which are of interest t...

Page 49: ...igger Options IEC 61850 has defined in total five different TrgOp Three of them belonging to data attributes and marked per data attribute in the column TrgOp of the CDC tables in part 7 3 The other t...

Page 50: ...ucture of the Report Control description of the IED section The description of the BRCB with selected DataSet configured parameters and selected IEDs is included in the SCL file in the IED section in...

Page 51: ...nput and output data values between IEDs on bay level in horizontal direction through the use of multicast services GOOSE messages enable fast transmission from a publisher to one or several subscribe...

Page 52: ...ver of the maximum time to wait for the next re transmission If a new message is not received within that time interval the receiver assumes that the association is lost The specific intervals used by...

Page 53: ...the send buffer with their actual value and the message is sent The subscribers who knows the address of this GOOSE message receives the telegram The GOOSE message includes a sequence number to verif...

Page 54: ...48...

Page 55: ...o IEC 61850 6 There are LN types based upon LN classes The LN type attributes are called Data Objects or DATA and are in of DO types base upon respective CDC class This allows all partners in the IEC...

Page 56: ...of SV IED configuration tool PCM600 or LHMI In case the setting operation of a function is set to Off from the LHMI or PCM600 the Beh will be set to Off independent of the value of the Mod The state...

Page 57: ...Mod Cmd Mode parameter Oper origin orIdent CO Mod Cmd Mode parameter Oper ctlNum CO Mod Cmd Mode parameter Oper T CO Mod Cmd Mode parameter Oper Test CO Mod Cmd Mode parameter Oper Check CO Mod Cmd M...

Page 58: ...Busbar voltage below the settable limit voltBusbBlockLimit HiTapPos b_dINS stVal ST Mon Tap position for max voltage q ST Mon Quality Tap position for max voltage t ST Mon Timestamp Tap position for m...

Page 59: ...0 Oper origin orCat CO Cmd Command parameter for IEC61850 Oper origin orIdent CO Cmd Command parameter for IEC61850 Oper ctlNum CO Cmd Command parameter for IEC61850 Oper T CO Cmd Command parameter fo...

Page 60: ...r IEC61850 Oper Check CO Cmd Command parameter for IEC61850 stVal ST Mon The setting LVAConst2 is used service value q ST Mon Quality The setting LVAConst2 is used service value t ST Mon Timestamp The...

Page 61: ...IEC61850 Oper origin orCat CO Cmd Command parameter for IEC61850 Oper origin orIdent CO Cmd Command parameter for IEC61850 Oper ctlNum CO Cmd Command parameter for IEC61850 Oper T CO Cmd Command para...

Page 62: ...veRev q ST QLTREV Mon Quality Reactive power below the settable limit powerReactiveRev t ST QLTREV Mon Timestamp Reactive power below the settable limit powerReactiveRev HiABlk v1_dSPS stVal ST IBLK M...

Page 63: ...ons within the time sliding window t ST HUNTING Mon Timestamp Alarm for too many contradictory tap changer operations within the time sliding window TotBlock v1_dSPS stVal ST TOTBLK Mon Block of auto...

Page 64: ...by user q MX Mon Quality Voltage setpoint set by user t MX Mon Timestamp Voltage setpoint set by user LVA1V v2_dMV mag f MX Mon Value 1 for load voltage adjustment q MX Mon Quality Value 1 for load v...

Page 65: ...Quality Group connection to horizontal communication and YLTCIN t MX ATCCOUT Mon Timestamp Group connection to horizontal communication and YLTCIN SetV v6_dMV mag f MX ATCCOUT Mon Group connection to...

Page 66: ...for IEC61850 Oper Check CO Cmd Command parameter for IEC61850 q ST Mon Quality Tap position t ST Mon Timestamp Tap position Mod a_dINC Oper ctlVal CO Mod Cmd Mode parameter Oper origin orCat CO Mod Cm...

Page 67: ...Timestamp Local commands selected BlkV a_dSPS stVal ST UBLK Mon Busbar voltage below the settable limit voltBusbBlockLimit q ST UBLK Mon Quality Busbar voltage below the settable limit voltBusbBlockL...

Page 68: ...mestamp Calculated reactive power service value ParOp c_dSPC stVal ST PARALLEL Mon The transformer operates in parallel mode q ST PARALLEL Mon Quality The transformer operates in parallel mode t ST PA...

Page 69: ...C61850 Oper Test CO Cmd Command parameter for IEC61850 Oper Check CO Cmd Command parameter for IEC61850 stVal ST Mon The setting LVAConst1 is used service value q ST Mon Quality The setting LVAConst1...

Page 70: ...e value t ST Mon Timestamp The setting LVAConst3 is used service value LVA4On v1_dSPC Oper ctlVal CO Cmd Command parameter for IEC61850 Oper origin orCat CO Cmd Command parameter for IEC61850 Oper ori...

Page 71: ...o be master q ST Mon Quality The transformer is forced to be master t ST Mon Timestamp The transformer is forced to be master HiV v1_dSPS stVal ST UHIGH Mon Busbar voltage above the settable limit vol...

Page 72: ...d in parallel group t ST T2PG Mon Timestamp Transformer2 included in parallel group T3ParGr v1_dSPS stVal ST T3PG Mon Transformer3 included in parallel group q ST T3PG Mon Quality Transformer3 include...

Page 73: ...ster t ST Mon Timestamp Transformer 2 is master T3Master v1_dSPS stVal ST Mon Transformer 3 is master q ST Mon Quality Transformer 3 is master t ST Mon Timestamp Transformer 3 is master T4Master v1_dS...

Page 74: ...PS stVal ST PLTREV Mon Active power below the settable limit powerActiveRev q ST PLTREV Mon Quality Active power below the settable limit powerActiveRev t ST PLTREV Mon Timestamp Active power below th...

Page 75: ...caused by reversed action Adapt v1_dSPS stVal ST ADAPT Mon The transformer is adapting q ST ADAPT Mon Quality The transformer is adapting t ST ADAPT Mon Timestamp The transformer is adapting DayHuntA...

Page 76: ...nds q ST TOTBLK Mon Quality Block of auto and manual commands t ST TOTBLK Mon Timestamp Block of auto and manual commands AutoBlock v1_dSPS stVal ST AUTOBLK Mon Block of auto commands q ST AUTOBLK Mon...

Page 77: ...CCAVolt Mon Quality Circulating Current Adjusted Voltage t MX CCAVolt Mon Timestamp Circulating Current Adjusted Voltage Q1VAr v2_dMV mag f MX Mon Size of reactive bank1 q MX Mon Quality Size of reac...

Page 78: ...Value 1 for load voltage adjustment LVA2V v2_dMV mag f MX Mon Value 2 for load voltage adjustment q MX Mon Quality Value 2 for load voltage adjustment t MX Mon Timestamp Value 2 for load voltage adjus...

Page 79: ...p connection to horizontal communication and YLTCIN t MX ATCCOUT Mon Timestamp Group connection to horizontal communication and YLTCIN SetV v6_dMV mag f MX ATCCOUT Mon Group connection to horizontal c...

Page 80: ...eter q ST Beh Mon Quality Behaviour parameter t ST Beh Mon Timestamp Behaviour parameter EndPosR a_dSPS stVal ST HIPOSAL Mon Alarm for tap in highest volt position q ST HIPOSAL Mon Quality Alarm for t...

Page 81: ...arameter for IEC61850 Oper origin orIdent CO Cmd Command parameter for IEC61850 Oper ctlNum CO Cmd Command parameter for IEC61850 Oper T CO Cmd Command parameter for IEC61850 Oper Test CO Cmd Command...

Page 82: ...al tap position change q ST TCERRAL Mon Quality Alarm for none or illegal tap position change t ST TCERRAL Mon Timestamp Alarm for none or illegal tap position change TapPosFlt v1_dSPS stVal ST POSERR...

Page 83: ...al Remote switch q ST Mon Quality Position of the Local Remote switch t ST Mon Timestamp Position of the Local Remote switch SrcOpPrm v1_dINS stVal ST PSTO Mon Value for the operator place allocation...

Page 84: ...lue used for blockUpdate stVal ST UPD_BLKD Mon Update of position is blocked q ST UPD_BLKD Mon Quality Update of position is blocked t ST UPD_BLKD Mon Timestamp Update of position is blocked BlkMeas v...

Page 85: ...er t ST Beh Mon Timestamp Behaviour parameter EnaCls aSPS stVal ST EN_CLOSE Mon Close operation at open or interm or bad pos is enabled q ST EN_CLOSE Mon Quality Close operation at open or interm or b...

Page 86: ...IEC61850 Oper ctlNum CO Cmd Command parameter for IEC61850 SBOw ctlNum CO Cmd Command parameter for IEC61850 SBOw T CO Cmd Command parameter for IEC61850 Cancel T CO Cmd Command parameter for IEC61850...

Page 87: ...haviour parameter for 61850 OpCls b_dACT general ST T EXE_CL Mon Execute command for close direction q ST T EXE_CL Mon Quality Execute command for close direction t ST T EXE_CL Mon Timestamp Execute c...

Page 88: ...stVal ST ACK_TO_B Mon Acknowledge to other bays that this bay is reserved q ST ACK_TO_B Mon Quality Acknowledge to other bays that this bay is reserved t ST ACK_TO_B Mon Timestamp Acknowledge to othe...

Page 89: ...d to operate t ST RES_GRT6 Mon Timestamp Reservation is made and the app 6 is allowed to operate PrmOp7 v1SPS stVal ST RES_GRT7 Mon Reservation is made and the app 7 is allowed to operate q ST RES_GRT...

Page 90: ...Check CO Mod Cmd Mode parameter stVal ST Mon Mode status parameter for 61850 q ST Mon Quality Mode status parameter for 61850 t ST Mon Timestamp Mode status parameter for 61850 Beh a_dINS stVal ST Beh...

Page 91: ...e FC T Signal Mon C md Description Mod a_dINC Oper ctlVal CO Mod Cmd Mode parameter Oper origin orCat CO Mod Cmd Mode parameter Oper origin orIdent CO Mod Cmd Mode parameter Oper ctlNum CO Mod Cmd Mod...

Page 92: ...ter Oper origin orCat CO Mod Cmd Mode parameter Oper origin orIdent CO Mod Cmd Mode parameter Oper ctlNum CO Mod Cmd Mode parameter Oper T CO Mod Cmd Mode parameter Oper Test CO Mod Cmd Mode parameter...

Page 93: ...v1SPS stVal ST TRNSSENS Mon Trip signal from sensitive neg seq diff protection q ST TRNSSENS Mon Quality Trip signal from sensitive neg seq diff protection t ST TRNSSENS Mon Timestamp Trip signal from...

Page 94: ...Mon Indication that internal fault has been detected q ST Mon Quality Indication that internal fault has been detected t ST Mon Timestamp Indication that internal fault has been detected Blk2HPhA v1SP...

Page 95: ...waveform criterion phase L1 BlkWavPhB v1SPS stVal ST BLKWAVL2 Mon Block signal waveform criterion phase L2 q ST BLKWAVL2 Mon Quality Block signal waveform criterion phase L2 t ST BLKWAVL2 Mon Timesta...

Page 96: ...from phase L3 q ST START Mon Quality Common start signal from any phase t ST START Mon Timestamp Common start signal from any phase Mod aINC Oper ctlVal CO Mod Cmd Mode parameter Oper origin orCat CO...

Page 97: ...ntial protection t ST TRIPRES Mon Timestamp Trip signal from restrained differential protection OpNSSen v1SPS stVal ST TRNSSENS Mon Trip signal from sensitive neg seq diff protection q ST TRNSSENS Mon...

Page 98: ...ication that external fault disturbance has been detected ItrFlt v1SPS stVal ST Mon Indication that internal fault has been detected q ST Mon Quality Indication that internal fault has been detected t...

Page 99: ...L1 Mon Timestamp Block signal waveform criterion phase L1 BlkWavPhB v1SPS stVal ST BLKWAVL2 Mon Block signal waveform criterion phase L2 q ST BLKWAVL2 Mon Quality Block signal waveform criterion phase...

Page 100: ...Oper Test CO Mod Cmd Mode parameter Oper Check CO Mod Cmd Mode parameter stVal ST Mon Mode status parameter for 61850 q ST Mon Quality Mode status parameter for 61850 t ST Mon Timestamp Mode status p...

Page 101: ...Common start signal from any phase phsA ST STL1 Mon Start signal from phase L1 phsB ST STL2 Mon Start signal from phase L2 phsC ST STL3 Mon Start signal from phase L3 q ST START Mon Quality Common st...

Page 102: ...for L3 q ST OPENCTPH Mon Quality Open CT in Phase 1 for L1 2 for L2 3 for L3 t ST OPENCTPH Mon Timestamp Open CT in Phase 1 for L1 2 for L2 3 for L3 OpRst v1SPS stVal ST TRIPRES Mon Trip signal from...

Page 103: ...ock signal t ST BLKH Mon Timestamp Common harmonic block signal BlkHPhA v1SPS stVal ST Mon Harmonic block signal phase L1 q ST Mon Quality Harmonic block signal phase L1 t ST Mon Timestamp Harmonic bl...

Page 104: ...DIF LN type LN prefix LN class Function block name HZPDIF revision 2 HZ PDIF HZPDIF Table 15 HZPDIF Logical node data DO name DO type DA name FC T Signal Mon C md Description Mod a_dINC Oper ctlVal CO...

Page 105: ...TRL2 Mon Check zone trip phase L2 phsC ST T TRL3 Mon Check zone trip phase L3 q ST T TRIP Mon Quality Check zone general trip t ST T TRIP Mon Timestamp Check zone general trip Beh aINS stVal ST Beh Mo...

Page 106: ...mp Common main start output signal Op a_dACT general ST T TRIP Mon Common main trip output signal phsA ST T TRL1 Mon Trip signal from phase L1 phsB ST T TRL2 Mon Trip signal from phase L2 phsC ST T TR...

Page 107: ...to 2nd harmonic t ST BLK2H Mon Timestamp Common block signal due to 2nd harmonic Blk5H v1_dSPS stVal ST BLK5H Mon Common block signal due to 5 th harmonic q ST BLK5H Mon Quality Common block signal d...

Page 108: ...L2 t ST BLK2HL2 Mon Timestamp Block signal due to 2nd harmonic phase L2 Blk2HPhC v1_dSPS stVal ST BLK2HL3 Mon Block signal due to 2nd harmonic phase L3 q ST BLK2HL3 Mon Quality Block signal due to 2n...

Page 109: ...signal phsA ST STL1 Mon Start signal from phase L1 phsB ST STL2 Mon Start signal from phase L2 phsC ST STL3 Mon Start signal from phase L3 q ST START Mon Quality Common main start output signal t ST S...

Page 110: ...e 1 for L1 2 for L2 3 for L3 t ST OPENCTPH Mon Timestamp Open CT in Phase 1 for L1 2 for L2 3 for L3 Blk2H v1_dSPS stVal ST BLK2H Mon Common block signal due to 2nd harmonic q ST BLK2H Mon Quality Com...

Page 111: ...2nd harmonic phase L1 t ST BLK2HL1 Mon Timestamp Block signal due to 2nd harmonic phase L1 Blk2HPhB v1_dSPS stVal ST BLK2HL2 Mon Block signal due to 2nd harmonic phase L2 q ST BLK2HL2 Mon Quality Blo...

Page 112: ...ith inzone transformers 23 line ends LT3CPDIF LN type LN prefix LN class Function block name LT3CPDIF revision 2 LT3C PDIF LT3CPDIF Table 20 LT3CPDIF Logical node data DO name DO type DA name FC T Sig...

Page 113: ...1 2 for input 2 q ST OPENCTIN Mon Quality Open CT on Input 1 for input 1 2 for input 2 t ST OPENCTIN Mon Timestamp Open CT on Input 1 for input 1 2 for input 2 OpnCTPh v1_dINS stVal ST OPENCTPH Mon O...

Page 114: ...tion q ST STARTUNR Mon Quality Start of unrestrained differential protection t ST STARTUNR Mon Timestamp Start of unrestrained differential protection Blk2HPhA v1_dSPS stVal ST BLK2HL1 Mon Block signa...

Page 115: ...dSPS stVal ST OPENCTAL Mon Open CT Alarm output signal Issued after a delay q ST OPENCTAL Mon Quality Open CT Alarm output signal Issued after a delay t ST OPENCTAL Mon Timestamp Open CT Alarm output...

Page 116: ...s parameter for 61850 Beh a_dINS stVal ST Beh Mon Behaviour parameter for 61850 q ST Beh Mon Quality Behaviour parameter for 61850 t ST Beh Mon Timestamp Behaviour parameter for 61850 OpnCTIn v1_dINS...

Page 117: ...ial protection q ST STARTRES Mon Quality Start of restrained differential protection t ST STARTRES Mon Timestamp Start of restrained differential protection StrUnRst v1_dSPS stVal ST STARTUNR Mon Star...

Page 118: ...ity An open CT was detected t ST OPENCT Mon Timestamp An open CT was detected OpnCTAlm v1_dSPS stVal ST OPENCTAL Mon Open CT Alarm output signal Issued after a delay q ST OPENCTAL Mon Quality Open CT...

Page 119: ...signal for low current criterion Startup v1_dSPS stVal ST START Mon General startup signal q ST START Mon Quality General startup signal t ST START Mon Timestamp General startup signal StUpCV1 v1_dSP...

Page 120: ...DO name DO type DA name FC T Signal Mon C md Description Str aACD general ST START Mon Start in any phase or loop dirGeneral ST Mon Integer coded info about general direction of fault phsA ST STNDL1 M...

Page 121: ...t ST STCNDZ Mon Timestamp Start condition Z with LE and 3I0 E F detection StrCndA v1INS stVal ST STCNDLE Mon Start condition only LE and 3I0 E F detection q ST STCNDLE Mon Quality Start condition onl...

Page 122: ...ty Fault detected in phase L3 reverse direction t ST STRVL3 Mon Timestamp Fault detected in phase L3 reverse direction StrRvGnd v1SPS stVal ST STRVPE Mon Earth fault detected in reverse direction q ST...

Page 123: ...Start in forward direction for thre phase fault t ST STFW3PH Mon Timestamp Start in forward direction for thre phase fault RelGnd v1SPS stVal ST STPE Mon Current conditions release of phase earth mea...

Page 124: ...ng has started Mod aINC Oper ctlVal CO Mod Cmd Mode parameter Oper origin orCat CO Mod Cmd Mode parameter Oper origin orIdent CO Mod Cmd Mode parameter Oper ctlNum CO Mod Cmd Mode parameter Oper T CO...

Page 125: ...p Common start signal Op b_dACT general ST T TRIP Mon Common trip signal q ST T TRIP Mon Quality Common trip signal t ST T TRIP Mon Timestamp Common trip signal OpZ1 v1_dSPS stVal ST TRZ1 Mon Trip sig...

Page 126: ...issued from any phase or loop dirGeneral ST Mon Integer coded info about general direction of fault phsA ST STL1 Mon Start signal from phase L1 phsB ST STL2 Mon Start signal from phase L2 phsC ST STL...

Page 127: ...ed from any phase or loop 7 5 3 5 Distance protection zone quadrilateral characteristic ZMQAPDIS LN type LN prefix LN class Function block name ZMQAPDIS revision 0 ZMQA PDIS ZMQAPDIS Table 27 ZMQAPDIS...

Page 128: ...h Mon Behaviour parameter q ST Beh Mon Quality Behaviour parameter t ST Beh Mon Timestamp Behaviour parameter StrNDir v1SPS stVal ST STND Mon Non directional start issued from any phase or loop q ST S...

Page 129: ...Mode parameter Oper ctlNum CO Mod Cmd Mode parameter Oper T CO Mod Cmd Mode parameter Oper Test CO Mod Cmd Mode parameter Oper Check CO Mod Cmd Mode parameter stVal ST Mon Mode status parameter for 61...

Page 130: ...or loop t ST T TRIP Mon Timestamp General Trip issued from any phase or loop Mod aINC Oper ctlVal CO Mod Cmd Mode parameter Oper origin orCat CO Mod Cmd Mode parameter Oper origin orIdent CO Mod Cmd...

Page 131: ...r Oper origin orCat CO Mod Cmd Mode parameter Oper origin orIdent CO Mod Cmd Mode parameter Oper ctlNum CO Mod Cmd Mode parameter Oper T CO Mod Cmd Mode parameter Oper Test CO Mod Cmd Mode parameter O...

Page 132: ...om phase L1 phsB ST STL2 Mon Start signal from phase L2 phsC ST STL3 Mon Start signal from phase L3 q ST START Mon Quality General Start issued from any phase or loop t ST START Mon Timestamp General...

Page 133: ...IS revision 0 ZMMA PDIS ZMMAPDIS Table 32 ZMMAPDIS Logical node data DO name DO type DA name FC T Signal Mon C md Description Str aACD general ST START Mon General Start issued from any phase or loop...

Page 134: ...nal start issued from any phase or loop q ST STND Mon Quality Non directional start issued from any phase or loop t ST STND Mon Timestamp Non directional start issued from any phase or loop 7 5 3 11 D...

Page 135: ...Oper Test CO Mod Cmd Mode parameter Oper Check CO Mod Cmd Mode parameter stVal ST Mon Mode status parameter for 61850 q ST Mon Quality Mode status parameter for 61850 t ST Mon Timestamp Mode status pa...

Page 136: ...TRIP Mon Timestamp General Trip issued from any phase or loop Mod aINC Oper ctlVal CO Mod Cmd Mode parameter Oper origin orCat CO Mod Cmd Mode parameter Oper origin orIdent CO Mod Cmd Mode parameter O...

Page 137: ...on Direction in phase L1 phsB ST STNDL2 Mon Fault detected in phase L2 any direction dirPhsB ST L2Dir Mon Direction in phase L2 phsC ST STNDL3 Mon Fault detected in phase L3 any direction dirPhsC ST L...

Page 138: ...Oper Test CO Mod Cmd Mode parameter for 61850 Oper Check CO Mod Cmd Mode parameter for 61850 stVal ST Mon Mode status value parameter for 61850 q ST Mon Quality Mode status value parameter for 61850 t...

Page 139: ...node data instance 2 DO name DO type DA name FC T Signal Mon C md Description Beh a_dINS stVal ST Beh Mon Behaviour parameter for 61850 q ST Beh Mon Quality Behaviour parameter for 61850 t ST Beh Mon...

Page 140: ...ection dirGeneral ST Mon Integer binary coded info about general direction of fault q ST STARTZ3 Mon Quality Start in any phase or phases from zone 3 zone direction t ST STARTZ3 Mon Timestamp Start in...

Page 141: ...ases from zone 4 zone direction t ST T TRIPZ4 Mon Timestamp Trip in any phase or phases from zone 4 zone direction Mod c_dINC stVal ST Mon Mode status value parameter for 61850 q ST Mon Quality Mode s...

Page 142: ...on Quality Behaviour parameter for 61850 t ST Beh Mon Timestamp Behaviour parameter for 61850 Str b_dACD general ST STARTZRV Mon Start in any phase or phases from zone RV reverse dir dirGeneral ST Mon...

Page 143: ...phase or loop t ST START Mon Timestamp Start in any phase or loop Mod aINC Oper ctlVal CO Mod Cmd Mode parameter for 61850 Oper origin orCat CO Mod Cmd Mode parameter for 61850 Oper origin orIdent CO...

Page 144: ...n t ST STFWL2 Mon Timestamp Fault detected in phase L2 forward direction StrFwdPhC v1SPS stVal ST STFWL3 Mon Fault detected in phase L3 forward direction q ST STFWL3 Mon Quality Fault detected in phas...

Page 145: ...Quality Non directional start in L3 t ST STNDL3 Mon Timestamp Non directional start in L3 StrNDGnd v1SPS stVal ST STNDPE Mon Non directional start phase earth q ST STNDPE Mon Quality Non directional...

Page 146: ...PDIS ZMFCLLN0 instance 1 revision 0 LLN0 ZMFCPDIS ZMFPDIS instance 1 revision 0 ZMF PDIS ZMFCPDIS ZMFPDIS instance 2 revision 0 ZMF PDIS ZMFCPDIS ZMFPDIS instance 3 revision 0 ZMF PDIS ZMFCPDIS ZMFPDI...

Page 147: ...r parameter for 61850 q ST Beh Mon Quality Behaviour parameter for 61850 t ST Beh Mon Timestamp Behaviour parameter for 61850 Mod c_dINC stVal ST Mon Mode status value parameter for 61850 q ST Mon Qua...

Page 148: ...from zone 1 forward direction dirGeneral ST Mon Integer binary coded info about general direction of fault q ST STARTZ1 Mon Quality Start in any phase or phases from zone 1 forward direction t ST STAR...

Page 149: ...phases from zone 2 forward direction t ST T TRIPZ2 Mon Timestamp Trip in any phase or phases from zone 2 forward direction Mod c_dINC stVal ST Mon Mode status value parameter for 61850 q ST Mon Quali...

Page 150: ...Quality Behaviour parameter for 61850 t ST Beh Mon Timestamp Behaviour parameter for 61850 Str b_dACD general ST STARTZ4 Mon Start in any phase or phases from zone 4 zone direction dirGeneral ST Mon I...

Page 151: ...RIPZ5 Mon Timestamp Trip in any phase or phases from zone 5 zone direction Mod c_dINC stVal ST Mon Mode status value parameter for 61850 q ST Mon Quality Mode status value parameter for 61850 t ST Mon...

Page 152: ...S ZGVPDIS ZGVPDIS instance 2 revision 0 ZGV PDIS ZGVPDIS ZGVPDIS instance 3 revision 0 ZGV PDIS ZGVPDIS ZGVPTUV instance 1 revision 0 ZGV PTUV ZGVPDIS Table 52 ZGVPDIS Logical node data instance 1 DO...

Page 153: ...haviour parameter for 61850 t ST Beh Mon Timestamp Behaviour parameter for 61850 Table 54 ZGVPDIS Logical node data instance 1 DO name DO type DA name FC T Signal Mon C md Description Beh a_dINS stVal...

Page 154: ...Timestamp Mode status value parameter for 61850 Table 56 ZGVPDIS Logical node data instance 3 DO name DO type DA name FC T Signal Mon C md Description Beh a_dINS stVal ST Beh Mon Behaviour parameter f...

Page 155: ...e parameter for 61850 q ST Mon Quality Mode status value parameter for 61850 t ST Mon Timestamp Mode status value parameter for 61850 7 5 4 Directional overpower PDOP 7 5 4 1 Directional over power pr...

Page 156: ...pZ2 v1_dSPS stVal ST TRIP2 Mon Trip of stage 2 q ST TRIP2 Mon Quality Trip of stage 2 t ST TRIP2 Mon Timestamp Trip of stage 2 StrZ1 v1_dSPS stVal ST START1 Mon Start of stage 1 q ST START1 Mon Qualit...

Page 157: ...Mon Common trip signal q ST T TRIP Mon Quality Common trip signal t ST T TRIP Mon Timestamp Common trip signal OpZ1 v1_dSPS stVal ST TRIP1 Mon Trip of stage 1 q ST TRIP1 Mon Quality Trip of stage 1 t...

Page 158: ...h Mon Behaviour parameter for 61850 q ST Beh Mon Quality Behaviour parameter for 61850 t ST Beh Mon Timestamp Behaviour parameter for 61850 Str b_dACD general ST START Mon Start pick up signal for fre...

Page 159: ...Mode parameter for 61850 Oper T CO Mod Cmd Mode parameter for 61850 Oper Test CO Mod Cmd Mode parameter for 61850 Oper Check CO Mod Cmd Mode parameter for 61850 stVal ST Mon Mode status value paramet...

Page 160: ...ion Op aACT general ST T TRIP Mon Trip signal from any phase phsA ST T TRL1 Mon Trip signal from phase L1 phsB ST T TRL2 Mon Trip signal from phase L2 phsC ST T TRL3 Mon Trip signal from phase L3 q ST...

Page 161: ...Mode parameter Oper T CO Mod Cmd Mode parameter Oper Test CO Mod Cmd Mode parameter Oper Check CO Mod Cmd Mode parameter stVal ST Mon Mode status parameter for 61850 q ST Mon Quality Mode status param...

Page 162: ...ST TRLL Mon Trip by loss of load q ST TRLL Mon Quality Trip by loss of load t ST TRLL Mon Timestamp Trip by loss of load OpZnExd v2ACT general ST TRZE Mon Trip by zone extension q ST TRZE Mon Quality...

Page 163: ...from remote end t ST T Mon Timestamp Teleprotection permissive signal received from remote end ProTx a_dSPS stVal ST T Mon Teleprotection permissive signal transmitted to remote end q ST T Mon Qualit...

Page 164: ...ST T TRWEIL2 Mon Trip signal from weak end infeed logic in phase L2 phsC ST T TRWEIL3 Mon Trip signal from weak end infeed logic in phase L3 q ST T TRWEI Mon Quality Trip signal from weak end infeed...

Page 165: ...stamp Carrier send by WEI logic Echo b_dACT general ST ECHO Mon Carrier send by WEI logic q ST ECHO Mon Quality Carrier send by WEI logic t ST ECHO Mon Timestamp Carrier send by WEI logic RvABlk b_dAC...

Page 166: ...al received from remote end t ST T Mon Timestamp Teleprotection permissive signal received from remote end ProTx a_dSPS stVal ST T Mon Teleprotection permissive signal transmitted to remote end q ST T...

Page 167: ...Val CO Mod Cmd Mode parameter Oper origin orCat CO Mod Cmd Mode parameter Oper origin orIdent CO Mod Cmd Mode parameter Oper ctlNum CO Mod Cmd Mode parameter Oper T CO Mod Cmd Mode parameter Oper Test...

Page 168: ...ogic t ST T TRWEI Mon Timestamp Trip signal from weak end infeed logic RvABlk b_dACT general ST IRVL Mon Operation of current reversal logic q ST IRVL Mon Quality Operation of current reversal logic t...

Page 169: ...Mon Quality Mode status parameter for 61850 t ST Mon Timestamp Mode status parameter for 61850 Beh aINS stVal ST Beh Mon Behaviour parameter q ST Beh Mon Quality Behaviour parameter t ST Beh Mon Time...

Page 170: ...850 Oper Test CO Mod Cmd Mode parameter for 61850 Oper Check CO Mod Cmd Mode parameter for 61850 stVal ST Mon Mode status parameter for 61850 q ST Mon Quality Mode status parameter for 61850 t ST Mon...

Page 171: ...er swing t ST CS Mon Timestamp Carrier send signal controlled by the power swing 7 5 10 7 Phase segregated Scheme communication logic for distance protection ZC1PPSCH LN type LN prefix LN class Functi...

Page 172: ...in Phase L2 phsC ST T TRL3 Mon Trip output in Phase L3 q ST T TRIP Mon Quality Common trip output in any of the phase t ST T TRIP Mon Timestamp Common trip output in any of the phase Mod aINC Oper ctl...

Page 173: ...ECHO Mon Carrier Send by WEI logic phsA ST ECHOL1 Mon Carrier Send by WEI logic in Phase L1 phsB ST ECHOL2 Mon Carrier Send by WEI logic in Phase L2 phsC ST ECHOL3 Mon Carrier Send by WEI logic in Ph...

Page 174: ...tatus parameter for 61850 t ST Mon Timestamp Mode status parameter for 61850 Beh aINS stVal ST Beh Mon Behaviour parameter q ST Beh Mon Quality Behaviour parameter t ST Beh Mon Timestamp Behaviour par...

Page 175: ...Mon Direction of fault A general signal common to all three mode of residual over current protection q ST START Mon Quality General start of the function t ST START Mon Timestamp General start of the...

Page 176: ...ion t ST TRDIRIN Mon Timestamp Trip of the directional residual over current function AngAV v2_dMV mag f MX ANG FI RCA Mon Angle between 3U0 and 3I0 minus RCA Fi RCA q MX ANG FI RCA Mon Quality Angle...

Page 177: ...or 61850 t ST Mon Timestamp Mode status parameter for 61850 Beh aINS stVal ST Beh Mon Behaviour parameter q ST Beh Mon Quality Behaviour parameter t ST Beh Mon Timestamp Behaviour parameter Op bACT ge...

Page 178: ...eh aINS stVal ST Beh Mon Behaviour parameter for 61850 q ST Beh Mon Quality Behaviour parameter for 61850 t ST Beh Mon Timestamp Behaviour parameter for 61850 IvdCrv v1SPS stVal ST Mon Invalid coeffic...

Page 179: ...ion q ST TRSOTF Mon Quality Trip signal from earth fault switch onto fault function t ST TRSOTF Mon Timestamp Trip signal from earth fault switch onto fault function Table 77 EF4PTOC Logical node data...

Page 180: ...Logical node data instance 1 DO name DO type DA name FC T Signal Mon C md Description Beh a_dINS stVal ST Beh Mon Behaviour parameter for 61850 q ST Beh Mon Quality Behaviour parameter for 61850 t ST...

Page 181: ...Timestamp Mode status value parameter for 61850 Table 81 EF4PTOC Logical node data instance 3 DO name DO type DA name FC T Signal Mon C md Description Beh a_dINS stVal ST Beh Mon Behaviour parameter f...

Page 182: ...LN type LN prefix LN class Function block name GEN4PHAR instance 1 revision 3 GEN4 PHAR OC4PTOC OC4LLN0 instance 1 revision 0 LLN0 OC4PTOC PH3PTOC instance 1 revision 0 PH3 PTOC OC4PTOC PH3PTOC instan...

Page 183: ...tamp Mode status parameter for 61850 Beh aINS stVal ST Beh Mon Behaviour parameter for 61850 q ST Beh Mon Quality Behaviour parameter for 61850 t ST Beh Mon Timestamp Behaviour parameter for 61850 Ivd...

Page 184: ...TOC Logical node data instance 2 DO name DO type DA name FC T Signal Mon C md Description Str aACD general ST ST2 Mon Common start signal from step2 phsA ST ST2L1 Mon Start signal from step2 phase L1...

Page 185: ...tart signal from step3 t ST ST3 Mon Timestamp Common start signal from step3 Op aACT general ST T TR3 Mon Common trip signal from step3 phsA ST T TR3L1 Mon Trip signal from step3 phase L1 phsB ST T TR...

Page 186: ...meter for 61850 q ST Beh Mon Quality Behaviour parameter for 61850 t ST Beh Mon Timestamp Behaviour parameter for 61850 Mod cINC stVal ST Mon Mode status parameter for 61850 q ST Mon Quality Mode stat...

Page 187: ...name DO type DA name FC T Signal Mon C md Description Str aACD general ST START Mon General start dirGeneral ST Mon Output for reporting the fault type undir during start phsA ST Mon Start signal fro...

Page 188: ...name FC T Signal Mon C md Description Mod a_dINC Oper ctlVal CO Mod Cmd Mode parameter Oper origin orCat CO Mod Cmd Mode parameter Oper origin orIdent CO Mod Cmd Mode parameter Oper ctlNum CO Mod Cmd...

Page 189: ...quence time overcurrent protection for machines NS2PTOC LN type LN prefix LN class Function block name NS2LLN0 instance 1 revision 1 LLN0 NS2PTOC NS2PTOC instance 1 revision 1 NS2 PTOC NS2PTOC NS2PTOC...

Page 190: ...NS2PTOC Logical node data instance 1 DO name DO type DA name FC T Signal Mon C md Description Beh a_dINS stVal ST Beh Mon Behaviour parameter for 61850 q ST Beh Mon Quality Behaviour parameter for 61...

Page 191: ...ble 95 NS2PTOC Logical node data instance 1 DO name DO type DA name FC T Signal Mon C md Description Beh a_dINS stVal ST Beh Mon Behaviour parameter for 61850 q ST Beh Mon Quality Behaviour parameter...

Page 192: ...eter for 61850 Oper origin orCat CO Mod Cmd Mode parameter for 61850 Oper origin orIdent CO Mod Cmd Mode parameter for 61850 Oper ctlNum CO Mod Cmd Mode parameter for 61850 Oper T CO Mod Cmd Mode para...

Page 193: ...q ST Beh Mon Quality Behaviour parameter for 61850 t ST Beh Mon Timestamp Behaviour parameter for 61850 Op b_dACT general ST T TRIP Mon Trip signal negative sequence over current protection q ST T TRI...

Page 194: ...t protection q ST T TRIP Mon Quality Trip signal for zero sequence over current protection t ST T TRIP Mon Timestamp Trip signal for zero sequence over current protection Str d_dACD general ST START M...

Page 195: ...Mon Timestamp Behaviour parameter for 61850 IvdCrv v1SPS stVal ST Mon Invalid coefficients for user programmable curve q ST Mon Quality Invalid coefficients for user programmable curve t ST Mon Times...

Page 196: ...on coded as integer t ST Mon Timestamp Fault direction coded as integer Mod c_dINC stVal ST Mon Mode status value parameter for 61850 q ST Mon Quality Mode status value parameter for 61850 t ST Mon Ti...

Page 197: ...Timestamp Mode status value parameter for 61850 Table 104 NS4PTOC Logical node data instance 2 DO name DO type DA name FC T Signal Mon C md Description Beh a_dINS stVal ST Beh Mon Behaviour parameter...

Page 198: ...Timestamp Mode status value parameter for 61850 Table 106 NS4PTOC Logical node data instance 4 DO name DO type DA name FC T Signal Mon C md Description Beh a_dINS stVal ST Beh Mon Behaviour parameter...

Page 199: ...ST ST2NDHRM Mon Second harmonic detected q ST ST2NDHRM Mon Quality Second harmonic detected t ST ST2NDHRM Mon Timestamp Second harmonic detected Mod c_dINC stVal ST Mon Mode status parameter for 6185...

Page 200: ...signal from step1 phase L2 phsC ST ST1L3 Mon Start signal from step1 phase L3 q ST ST1 Mon Quality Common start signal from step1 t ST ST1 Mon Timestamp Common start signal from step1 Op aACT general...

Page 201: ...er for 61850 q ST Beh Mon Quality Behaviour parameter for 61850 t ST Beh Mon Timestamp Behaviour parameter for 61850 Mod cINC stVal ST Mon Mode status parameter for 61850 q ST Mon Quality Mode status...

Page 202: ...1 phsB ST ST4L2 Mon Start signal from step4 phase L2 phsC ST ST4L3 Mon Start signal from step4 phase L3 q ST ST4 Mon Quality Common start signal from step4 t ST ST4 Mon Timestamp Common start signal f...

Page 203: ...TRIP Mon Timestamp Trip Beh aINS stVal ST Beh Mon Behaviour parameter for 61850 q ST Beh Mon Quality Behaviour parameter for 61850 t ST Beh Mon Timestamp Behaviour parameter for 61850 Mod cINC stVal S...

Page 204: ...aINC Oper ctlVal CO Mod Cmd Mode parameter Oper origin orCat CO Mod Cmd Mode parameter Oper origin orIdent CO Mod Cmd Mode parameter Oper ctlNum CO Mod Cmd Mode parameter Oper T CO Mod Cmd Mode param...

Page 205: ...T Mon Timestamp Mode status parameter for 61850 Table 117 PH4SPTOC Logical node data instance 2 DO name DO type DA name FC T Signal Mon C md Description Beh a_dINS stVal ST Beh Mon Behaviour parameter...

Page 206: ...T Mon Timestamp Mode status parameter for 61850 Table 119 PH4SPTOC Logical node data instance 4 DO name DO type DA name FC T Signal Mon C md Description Beh a_dINS stVal ST Beh Mon Behaviour parameter...

Page 207: ...EF4LLN0 instance 1 revision 1 LLN0 EF4PTOC EF4PTRC instance 1 revision 3 EF4 PTRC EF4PTOC EF4RDIR instance 1 revision 6 EF4 RDIR EF4PTOC GEN4PHAR instance 1 revision 3 GEN4 PHAR EF4PTOC PH1PTOC insta...

Page 208: ...61850 q ST Beh Mon Quality Behaviour parameter for 61850 t ST Beh Mon Timestamp Behaviour parameter for 61850 Str b_dACD general ST START Mon General start signal q ST START Mon Quality General start...

Page 209: ...direction coded as integer Mod c_dINC stVal ST Mon Mode status value parameter for 61850 q ST Mon Quality Mode status value parameter for 61850 t ST Mon Timestamp Mode status value parameter for 6185...

Page 210: ...Timestamp Mode status value parameter for 61850 Table 126 EF4PTOC Logical node data instance 2 DO name DO type DA name FC T Signal Mon C md Description Beh a_dINS stVal ST Beh Mon Behaviour parameter...

Page 211: ...Timestamp Mode status value parameter for 61850 Table 128 EF4PTOC Logical node data instance 4 DO name DO type DA name FC T Signal Mon C md Description Beh a_dINS stVal ST Beh Mon Behaviour parameter...

Page 212: ...ameter for 61850 q ST Mon Quality Mode status value parameter for 61850 t ST Mon Timestamp Mode status value parameter for 61850 Beh a_dINS stVal ST Beh Mon Behaviour parameter for 61850 q ST Beh Mon...

Page 213: ...0 t ST Beh Mon Timestamp Behaviour parameter for 61850 Str b_dACD general ST START Mon General start signal q ST START Mon Quality General start signal t ST START Mon Timestamp General start signal Op...

Page 214: ...al ST T TRIP Mon Trip signal for negative sequence over voltage q ST T TRIP Mon Quality Trip signal for negative sequence over voltage t ST T TRIP Mon Timestamp Trip signal for negative sequence over...

Page 215: ...IP signal for zero sequence over voltage protection Str d_dACD general ST START Mon Start signal for zero sequence over voltage protection q ST START Mon Quality Start signal for zero sequence over vo...

Page 216: ...1L2 Mon Start signal from step1 phase L2 phsC ST ST1L3 Mon Start signal from step1 phase L3 q ST ST1 Mon Quality Common start signal from step1 t ST ST1 Mon Timestamp Common start signal from step1 Op...

Page 217: ...r parameter q ST Beh Mon Quality Behaviour parameter t ST Beh Mon Timestamp Behaviour parameter Mod cINC stVal ST Mon Mode status parameter for 61850 q ST Mon Quality Mode status parameter for 61850 t...

Page 218: ...ter for 61850 stVal ST Mon Mode status value parameter for 61850 q ST Mon Quality Mode status value parameter for 61850 t ST Mon Timestamp Mode status value parameter for 61850 Beh a_dINS stVal ST Beh...

Page 219: ...start signal from step1 Op b_dACT general ST T TR1 Mon Common trip signal from step1 q ST T TR1 Mon Quality Common trip signal from step1 t ST T TR1 Mon Timestamp Common trip signal from step1 Mod c_d...

Page 220: ...T Signal Mon C md Description Mod a_dINC Oper ctlVal CO Mod Cmd Mode parameter Oper origin orCat CO Mod Cmd Mode parameter Oper origin orIdent CO Mod Cmd Mode parameter Oper ctlNum CO Mod Cmd Mode par...

Page 221: ...p phase 2 phsC ST TRL3 Mon Trip phase 3 q ST TRIP Mon Quality Common trip t ST TRIP Mon Timestamp Common trip Mod a_dINC Oper ctlVal CO Mod Cmd Mode parameter for 61850 Oper origin orCat CO Mod Cmd Mo...

Page 222: ...ode parameter Oper T CO Mod Cmd Mode parameter Oper Test CO Mod Cmd Mode parameter Oper Check CO Mod Cmd Mode parameter stVal ST Mon Mode status parameter for 61850 q ST Mon Quality Mode status parame...

Page 223: ...Timestamp Circuit breaker lockout output set until reset 7 5 17 Thermal overload PTTR 7 5 17 1 Thermal overload protection one time constant Celsius LCPTTR LN type LN prefix LN class Function block n...

Page 224: ...Mon Temperature relative to operate temperature q MX TERMLOAD Mon Quality Temperature relative to operate temperature t MX TERMLOAD Mon Timestamp Temperature relative to operate temperature TmmOp v1_d...

Page 225: ...igin orIdent CO Mod Cmd Mode parameter Oper ctlNum CO Mod Cmd Mode parameter Oper T CO Mod Cmd Mode parameter Oper Test CO Mod Cmd Mode parameter Oper Check CO Mod Cmd Mode parameter stVal ST Mon Mode...

Page 226: ...to reset of lockout in min q ST TENRECL Mon Quality Estimated time to reset of lockout in min t ST TENRECL Mon Timestamp Estimated time to reset of lockout in min BlkRecSt v1_dSPS stVal ST LOCKOUT Mo...

Page 227: ...l t ST ALARM2 Mon Timestamp Second level alarm signal AlmThm a_dSPS stVal ST ALARM1 Mon First level alarm signal q ST ALARM1 Mon Quality First level alarm signal t ST ALARM1 Mon Timestamp First level...

Page 228: ...HEATCONT Mon Quality Percentage of the heat content of the transformer t MX HEATCONT Mon Timestamp Percentage of the heat content of the transformer 7 5 17 4 Rotor overload protection GRPTTR LN type...

Page 229: ...hine closing command LO v1_dSPS stVal ST LOCKOUT Mon Trip lockout output latched q ST LOCKOUT Mon Quality Trip lockout output latched t ST LOCKOUT Mon Timestamp Trip lockout output latched AlmRpl v1_d...

Page 230: ...de parameter for 61850 Oper ctlNum CO Mod Cmd Mode parameter for 61850 Oper T CO Mod Cmd Mode parameter for 61850 Oper Test CO Mod Cmd Mode parameter for 61850 Oper Check CO Mod Cmd Mode parameter for...

Page 231: ...n percent of set trip level i e Trip 100 7 5 18 Three phase undercurrent PTUC 7 5 18 1 Three phase undercurrent LCP3PTUC LN type LN prefix LN class Function block name LCP3PTUC revision 0 LCP3 PTUC LC...

Page 232: ...Beh Mon Quality Behaviour parameter for 61850 t ST Beh Mon Timestamp Behaviour parameter for 61850 7 5 19 Undervoltage PTUV 7 5 19 1 Two step undervoltage protection UV2PTUV LN type LN prefix LN clas...

Page 233: ...General start signal Op b_dACT general ST TRIP Mon Trip q ST TRIP Mon Quality Trip t ST TRIP Mon Timestamp Trip Mod c_dINC stVal ST Mon Mode status parameter for 61850 q ST Mon Quality Mode status pa...

Page 234: ...t signal from step2 phase L1 phsB ST ST2L2 Mon Start signal from step2 phase L2 phsC ST ST2L3 Mon Start signal from step2 phase L3 q ST ST2 Mon Quality Common start signal from step2 t ST ST2 Mon Time...

Page 235: ...ode status parameter for 61850 q ST Mon Quality Mode status parameter for 61850 t ST Mon Timestamp Mode status parameter for 61850 Beh a_dINS stVal ST Beh Mon Behaviour parameter for 61850 q ST Beh Mo...

Page 236: ...arameter for 61850 Str b_dACD general ST START Mon General start signal q ST START Mon Quality General start signal t ST START Mon Timestamp General start signal Op b_dACT general ST T TRIP Mon Genera...

Page 237: ...Mon Quality Behaviour parameter t ST Beh Mon Timestamp Behaviour parameter Str b_dACD general ST START Mon Overexcitation above set operate level instantaneous q ST START Mon Quality Overexcitation a...

Page 238: ...d a_dINC Oper ctlVal CO Mod Cmd Mode parameter for 61850 Oper origin orCat CO Mod Cmd Mode parameter for 61850 Oper origin orIdent CO Mod Cmd Mode parameter for 61850 Oper ctlNum CO Mod Cmd Mode param...

Page 239: ...ntal energizing of generator protection is armed 7 5 22 2 Status of primary switching object for Busbar Protection Zone Selection BDCGAPC LN type LN prefix LN class Function block name SWSGGIO revisio...

Page 240: ...nction block name CBPLLN0 instance 1 revision 1 LLN0 CBPGAPC CBPMMXU instance 1 revision 1 CBP MMXU CBPGAPC CBPPTRC instance 1 revision 0 CBP PTRC CBPGAPC HOLPTOV instance 1 revision 1 HOL PTOV CBPGAP...

Page 241: ...850 Mod c_dINC stVal ST Mon Mode status value parameter for 61850 q ST Mon Quality Mode status value parameter for 61850 t ST Mon Timestamp Mode status value parameter for 61850 APeakPhA v2_dMV mag f...

Page 242: ...1 t MX QL1 Mon Timestamp Reactive power value for phase L1 VArPhB v2_dMV mag f MX QL2 Mon Reactive power value for phase L2 q MX QL2 Mon Quality Reactive power value for phase L2 t MX QL2 Mon Timestam...

Page 243: ...ta instance 1 DO name DO type DA name FC T Signal Mon C md Description Str a_dACD general ST STHOL Mon Start signal for harmonic over load phsA ST STHIDML1 Mon Start signal for harmonic over load IDMT...

Page 244: ...e 2 DO name DO type DA name FC T Signal Mon C md Description Str a_dACD general ST STHOL Mon Start signal for harmonic over load phsA ST STHDTL1 Mon Start signal harmonic over load Definite Time stage...

Page 245: ...uality Start signals for over current t ST STOC Mon Timestamp Start signals for over current Op a_dACT general ST T TROC Mon Trip signal for over current phsA ST T Mon Trip signal for over current of...

Page 246: ...r current t ST T TRUC Mon Timestamp Trip signal for under current Beh a_dINS stVal ST Beh Mon Behaviour parameter for 61850 q ST Beh Mon Quality Behaviour parameter for 61850 t ST Beh Mon Timestamp Be...

Page 247: ...22 4 Compensated over and undervoltage protection COUVGAPC LN type LN prefix LN class Function block name COUVLLN0 instance 1 revision 0 LLN0 COUVGAPC COUVPTOV instance 1 revision 0 COUV PTOV COUVGAPC...

Page 248: ...Common start signal for compensated over voltage phsA ST STOVL1 Mon Start signal for compensated over voltage of phase 1 phsB ST STOVL2 Mon Start signal for compensated over voltage of phase 2 phsC S...

Page 249: ...signal for compensated under voltage of phase 3 q ST STUV Mon Quality Common start signal for compensated under voltage t ST STUV Mon Timestamp Common start signal for compensated under voltage Mod c_...

Page 250: ...ck CO Mod Cmd Mode parameter stVal ST Mon Mode status parameter for 61850 q ST Mon Quality Mode status parameter for 61850 t ST Mon Timestamp Mode status parameter for 61850 Beh aINS stVal ST Beh Mon...

Page 251: ...rFact v2MV mag f MX ICOSFI Mon Measured current multiplied with cos Phi q MX ICOSFI Mon Quality Measured current multiplied with cos Phi t MX ICOSFI Mon Timestamp Measured current multiplied with cos...

Page 252: ...OV1 Mon Timestamp Start signal from overvoltage function OV1 Op b_dACT general ST T TROV1 Mon Trip signal from overvoltage function OV1 q ST T TROV1 Mon Quality Trip signal from overvoltage function O...

Page 253: ...Description Beh a_dINS stVal ST Beh Mon Behaviour parameter for 61850 q ST Beh Mon Quality Behaviour parameter for 61850 t ST Beh Mon Timestamp Behaviour parameter for 61850 Str b_dACD general ST STUC...

Page 254: ...r for 61850 q ST Mon Quality Mode status parameter for 61850 t ST Mon Timestamp Mode status parameter for 61850 Table 178 CVGAPC Logical node data instance 1 DO name DO type DA name FC T Signal Mon C...

Page 255: ...neral ST T TRUV2 Mon Trip signal from undervoltage function UV2 q ST T TRUV2 Mon Quality Trip signal from undervoltage function UV2 t ST T TRUV2 Mon Timestamp Trip signal from undervoltage function UV...

Page 256: ...ion OC2 Table 181 CVGAPC Logical node data instance 1 DO name DO type DA name FC T Signal Mon C md Description Beh a_dINS stVal ST Beh Mon Behaviour parameter for 61850 q ST Beh Mon Quality Behaviour...

Page 257: ...meter for 61850 Str b_dACD general ST START Mon General start signal q ST START Mon Quality General start signal t ST START Mon Timestamp General start signal Op b_dACT general ST TRIP Mon General tri...

Page 258: ...84 LAPPGAPC Logical node data instance 1 DO name DO type DA name FC T Signal Mon C md Description Str a_dACD general ST STLAP Mon Start low active power phsA ST STLAPL1 Mon Start low active power phas...

Page 259: ...haviour parameter for 61850 q ST Beh Mon Quality Behaviour parameter for 61850 t ST Beh Mon Timestamp Behaviour parameter for 61850 Mod c_dINC stVal ST Mon Mode status value parameter for 61850 q ST M...

Page 260: ...of time domained mho CarTcBlk v1SPS stVal ST BLKCHST Mon Blocking signal to remote end to block overreaching zone q ST BLKCHST Mon Quality Blocking signal to remote end to block overreaching zone t S...

Page 261: ...ehaviour parameter for 61850 Str b_dACD general ST TRIP Mon General trip q ST TRIP Mon Quality General trip t ST TRIP Mon Timestamp General trip Op e_dACT general ST T TRIP Mon General trip phsA ST T...

Page 262: ...tamp Mode status value parameter for 61850 Beh a_dINS stVal ST Beh Mon Behaviour parameter for 61850 q ST Beh Mon Quality Behaviour parameter for 61850 t ST Beh Mon Timestamp Behaviour parameter for 6...

Page 263: ...m during pole slip 7 5 23 2 PoleSlip Out of step protection PSPPPAM LN type LN prefix LN class Function block name PSPPPAM revision 3 PSP PPAM PSPPPAM Table 189 PSPPPAM Logical node data DO name DO ty...

Page 264: ...one2 q ST TRIP2 Mon Quality Trip2 after the N2Limit slip in zone2 t ST TRIP2 Mon Timestamp Trip2 after the N2Limit slip in zone2 SlpZ1 v1_dSPS stVal ST ZONE1 Mon First slip in zone1 region q ST ZONE1...

Page 265: ...parameter for 61850 Oper T CO Mod Cmd Mode parameter for 61850 Oper Test CO Mod Cmd Mode parameter for 61850 Oper Check CO Mod Cmd Mode parameter for 61850 stVal ST Mon Mode status value parameter fo...

Page 266: ...n Quality Start for AC side of exciter t ST STARTAC Mon Timestamp Start for AC side of exciter OpDC v2_dACT general ST TRIPDC Mon Trip for DC side of exciter q ST TRIPDC Mon Quality Trip for DC side o...

Page 267: ...amp Main common trip command Op3rdH v1_dSPS stVal ST TRIP3H Mon Trip by one of two 3rd harmonic voltage based prot q ST TRIP3H Mon Quality Trip by one of two 3rd harmonic voltage based prot t ST TRIP3...

Page 268: ...y Volts VDif3rdH v2_dMV mag f MX DU3 Mon Diff between 3rd harm volt at both sides of gen Volts q MX DU3 Mon Quality Diff between 3rd harm volt at both sides of gen Volts t MX DU3 Mon Timestamp Diff be...

Page 269: ...amp Mode status value parameter for 61850 Beh a_dINS stVal ST Beh Mon Behaviour parameter for 61850 q ST Beh Mon Quality Behaviour parameter for 61850 t ST Beh Mon Timestamp Behaviour parameter for 61...

Page 270: ...Behaviour parameter for 61850 Str b_dACD general ST START Mon General start signal q ST START Mon Quality General start signal t ST START Mon Timestamp General start signal Op b_dACT general ST TRIP M...

Page 271: ...61850 Table 195 VRPVOC Logical node data instance 1 DO name DO type DA name FC T Signal Mon C md Description Mod a_dINC Oper ctlVal CO Mod Cmd Mode parameter Oper origin orCat CO Mod Cmd Mode paramete...

Page 272: ...overcurrent stage t ST T TROC Mon Timestamp Trip signal from voltage restrained overcurrent stage Mod c_dINC stVal ST Mon Mode status parameter for 61850 q ST Mon Quality Mode status parameter for 61...

Page 273: ...rIdent CO Cmd Mapping tag Oper ctlNum CO Cmd Mapping tag Oper T CO Cmd Mapping tag Oper Test CO Cmd Mapping tag Oper Check CO Cmd Mapping tag stVal ST Mon Mapping tag q ST Mon Quality Mapping tag t ST...

Page 274: ...d Description Mod a_dINC Oper ctlVal CO Mod Cmd Mode parameter for 61850 Oper origin orCat CO Mod Cmd Mode parameter for 61850 Oper origin orIdent CO Mod Cmd Mode parameter for 61850 Oper ctlNum CO Mo...

Page 275: ...0 Oper Check CO Cmd Mode parameter for 61850 stVal ST Mon Mode status value parameter for 61850 q ST Mon Quality Mode status value parameter for 61850 t ST Mon Timestamp Mode status value parameter fo...

Page 276: ...ST T TRRETL3 Mon Retrip by breaker failure protection function phase L3 q ST T TRRET Mon Quality Retrip by breaker failure protection function t ST T TRRET Mon Timestamp Retrip by breaker failure prot...

Page 277: ...RBRF CCSRBRF Table 203 CCSRBRF Logical node data DO name DO type DA name FC T Signal Mon C md Description Mod aINC Oper ctlVal CO Mod Cmd Mode parameter Oper origin orCat CO Mod Cmd Mode parameter Op...

Page 278: ...me CCSRDIF revision 2 CCS RDIF CCSSPVC Table 204 CCSSPVC Logical node data DO name DO type DA name FC T Signal Mon C md Description Mod aINC Oper ctlVal CO Mod Cmd Mode parameter Oper origin orCat CO...

Page 279: ...d Mode parameter for 61850 Oper origin orIdent CO Mod Cmd Mode parameter for 61850 Oper ctlNum CO Mod Cmd Mode parameter for 61850 Oper T CO Mod Cmd Mode parameter for 61850 Oper Test CO Mod Cmd Mode...

Page 280: ...Oper Test CO Mod Cmd Mode parameter for 61850 Oper Check CO Mod Cmd Mode parameter for 61850 stVal ST Mon Mode status value parameter for 61850 q ST Mon Quality Mode status value parameter for 61850...

Page 281: ...FUFSPVC Logical node data DO name DO type DA name FC T Signal Mon C md Description Mod aINC Oper ctlVal CO Mod Cmd Mode parameter Oper origin orCat CO Mod Cmd Mode parameter Oper origin orIdent CO Mod...

Page 282: ...tr a_dACD general ST MAINFUF Mon Block of main fuse failure phsA ST U1L1FAIL Mon Fuse failure of Main fuse group phase L1 phsB ST U1L2FAIL Mon Fuse failure of Main fuse group phase L2 phsC ST U1L3FAIL...

Page 283: ...6 Pole discordance protection RPLD 7 7 6 1 Pole discordance protection CCPDSC LN type LN prefix LN class Function block name CCRPLD revision 0 CC RPLD CCPDSC Table 209 CCPDSC Logical node data DO nam...

Page 284: ...DO type DA name FC T Signal Mon C md Description Mod a_dINC Oper ctlVal CO Mod Cmd Mode parameter Oper origin orCat CO Mod Cmd Mode parameter Oper origin orIdent CO Mod Cmd Mode parameter Oper ctlNum...

Page 285: ...EC 7 7 8 1 SMBRREC LN type LN prefix LN class Function block name SMBRREC revision 1 SMB RREC SMBRREC Table 211 SMBRREC Logical node data DO name DO type DA name FC T Signal Mon C md Description Mod a...

Page 286: ...e reclosing shots Rec31Cnt v1INS stVal ST COUNT3P1 Mon Counting the number of three phase reclosing shot 1 q ST COUNT3P1 Mon Quality Counting the number of three phase reclosing shot 1 t ST COUNT3P1 M...

Page 287: ...Command parameter for IEC61850 Oper Check CO Cmd Command parameter for IEC61850 EnaRec v1SPS stVal ST SETON Mon The AR operation is switched on operative q ST SETON Mon Quality The AR operation is swi...

Page 288: ...sing is in progress shot 1 PrgRec21 v1SPS stVal ST 2PT1 Mon Two phase reclosing is in progress shot 1 q ST 2PT1 Mon Quality Two phase reclosing is in progress shot 1 t ST 2PT1 Mon Timestamp Two phase...

Page 289: ...rip control of the next trip operation q ST PREP3P Mon Quality Prepare three phase trip control of the next trip operation t ST PREP3P Mon Timestamp Prepare three phase trip control of the next trip o...

Page 290: ...ference out of limit for Auto operation VInd a_dSPS stVal ST UDIFFSC Mon Voltage difference out of limit q ST UDIFFSC Mon Quality Voltage difference out of limit t ST UDIFFSC Mon Timestamp Voltage dif...

Page 291: ...y Line voltage t MX ULINE Mon Timestamp Line voltage Table 213 SESRSYN Logical node data instance 2 DO name DO type DA name FC T Signal Mon C md Description Beh a_dINS stVal ST Beh Mon Behaviour param...

Page 292: ...Quality Manual synchro check OK test output t ST TSTMANSY Mon Timestamp Manual synchro check OK test output Table 214 SESRSYN Logical node data instance 1 DO name DO type DA name FC T Signal Mon C md...

Page 293: ...IL Mon Selected voltage transformer fuse failed q ST USELFAIL Mon Quality Selected voltage transformer fuse failed t ST USELFAIL Mon Timestamp Selected voltage transformer fuse failed TestEnOK v1_dSPS...

Page 294: ...estamp Synchronizing failed TestSynOK v1_dSPS stVal ST TSTSYNOK Mon Synchronizing OK test output q ST TSTSYNOK Mon Quality Synchronizing OK test output t ST TSTSYNOK Mon Timestamp Synchronizing OK tes...

Page 295: ...election and LHMI presentation SLGAPC LN type LN prefix LN class Function block name SLGGIO revision 4 SL GGIO SLGAPC Table 216 SLGAPC Logical node data DO name DO type DA name FC T Signal Mon C md De...

Page 296: ...ype for step cmd sboTimeout CF Maximum time between select and execute signals for step cmd sboClass CF Select for many used for step cmd SwPosC1 v3_dISC Oper ctlVal CO Cmd Command parameter for IEC61...

Page 297: ...eh Mon Behaviour parameter q ST Beh Mon Quality Behaviour parameter t ST Beh Mon Timestamp Behaviour parameter DPCSO d_dDPC Cancel ctlVal CO Cmd Command parameter for IEC61850 Cancel origin orCat CO C...

Page 298: ...imestamp Position indication integer stSeld ST Mon Select conditions are fulfilled ctlModel CF CtlModel Specifies the type for control model according to IEC 61850 7 8 1 3 Generic communication functi...

Page 299: ...A name FC T Signal Mon C md Description Mod a_dINC Oper ctlVal CO Mod Cmd Mode parameter for 61850 Oper origin orCat CO Mod Cmd Mode parameter for 61850 Oper origin orIdent CO Mod Cmd Mode parameter f...

Page 300: ...r IEC61850 Oper Test CO Cmd Command parameter for IEC61850 Oper Check CO Cmd Command parameter for IEC61850 SPCSO3 d_dSPC Oper ctlVal CO Cmd Command parameter for IEC61850 Oper origin orCat CO Cmd Com...

Page 301: ...meter for IEC61850 Oper origin orCat CO Cmd Command parameter for IEC61850 Oper origin orIdent CO Cmd Command parameter for IEC61850 Oper ctlNum CO Cmd Command parameter for IEC61850 Oper T CO Cmd Com...

Page 302: ...actVal ST VALUE Mon Counted value q ST VALUE Mon Quality Counted value t ST VALUE Mon Timestamp Counted value Mod a_dINC Oper ctlVal CO Mod Cmd Mode parameter for 61850 Oper origin orCat CO Mod Cmd M...

Page 303: ...MIT2 Mon Counted value is larger than or equal to CounterLimit2 q ST LIMIT2 Mon Quality Counted value is larger than or equal to CounterLimit2 t ST LIMIT2 Mon Timestamp Counted value is larger than or...

Page 304: ...50 Ind c_dSPS stVal ST OUT Mon Output status q ST OUT Mon Quality Output status t ST OUT Mon Timestamp Output status 7 8 1 7 IEC61850 generic communication I O functions 16 inputs SP16GGIO LN type LN...

Page 305: ...T OUT5 Mon Output 5 status q ST OUT5 Mon Quality Output 5 status t ST OUT5 Mon Timestamp Output 5 status Ind6 c_dSPS stVal ST OUT6 Mon Output 6 status q ST OUT6 Mon Quality Output 6 status t ST OUT6 M...

Page 306: ...Ind v1_dSPS stVal ST OUTOR Mon Output status logic OR gate for input 1 to 16 q ST OUTOR Mon Quality Output status logic OR gate for input 1 to 16 t ST OUTOR Mon Timestamp Output status logic OR gate f...

Page 307: ...MV llLim Low Low limit multiplied with the base prefix multiplication factor rangeC max f CF MV max Maximum value multiplied with the base prefix multiplication factor rangeC min f CF MV min Minimum...

Page 308: ...AL_VAL Mon Quality Scaled value with time and status information t MX SCAL_VAL Mon Timestamp Scaled value with time and status information TotVal v1BCR actVal ST CNT_VAL Mon Actual pulse counter value...

Page 309: ...ST Beh Mon Timestamp Behaviour parameter Out1 v1SPS stVal ST OUTPUT1 Mon OR function betweeen inputs 1 to 16 q ST OUTPUT1 Mon Quality OR function betweeen inputs 1 to 16 t ST OUTPUT1 Mon Timestamp OR...

Page 310: ...for 61850 Alm a_dSPS stVal ST ALARM Mon Indicator of the integrated time has reached the alarm limit q ST ALARM Mon Quality Indicator of the integrated time has reached the alarm limit t ST ALARM Mon...

Page 311: ...on Mod a_dINC Oper ctlVal CO Mod Cmd Mode parameter for 61850 Oper origin orCat CO Mod Cmd Mode parameter for 61850 Oper origin orIdent CO Mod Cmd Mode parameter for 61850 Oper ctlNum CO Mod Cmd Mode...

Page 312: ...ST ACCINPRG Mon Accumulation of energy values in progress q ST ACCINPRG Mon Quality Accumulation of energy values in progress t ST ACCINPRG Mon Timestamp Accumulation of energy values in progress WhF...

Page 313: ...R q ST Mon Quality Accumulated reverse reactive energy value BCR t ST Mon Timestamp Accumulated reverse reactive energy value BCR pulsQty CF ERRAccPlsQty Pulse quantity for reactive reverse accumulate...

Page 314: ...V mag f MX MAXPARD Mon Maximum reverse active power demand value for set interval q MX MAXPARD Mon Quality Maximum reverse active power demand value for set interval t MX MAXPARD Mon Timestamp Maximum...

Page 315: ...ated current range q MX I Mon Quality Calculated current magnitude of deadband value t MX I Mon Timestamp Calculated current magnitude of deadband value subEna SV Enable substitution db CF IDbRepInt C...

Page 316: ...stitution db CF PFDbRepInt Cycl Report interval s Db In of range Int Db In s zeroDb CF PFZeroDb Zero point clamping in 0 001 of range Vol a_dMV rangeC hhLim f CF UHiHiLim High High limit in of UBase r...

Page 317: ...High limit in of SBase rangeC hLim f CF QHiLim High limit in of SBase rangeC lLim f CF QLowLim Low limit in of SBase rangeC llLim f CF QLowLowLim Low Low limit in of SBase rangeC max f CF QMax Maximum...

Page 318: ...rent is leading voltage ALg v1_dSPS stVal ST ILAG Mon Current is lagging voltage q ST ILAG Mon Quality Current is lagging voltage t ST ILAG Mon Timestamp Current is lagging voltage 7 9 3 Measurement M...

Page 319: ...angeC lLim f CF IL2LowLim Low limit in of IBase rangeC llLim f CF IL2LowLowLim Low Low limit in of IBase rangeC max f CF IL2Max Maximum value in of IBase rangeC min f CF IL2Min Minimum value in of IBa...

Page 320: ...clamping zeroDb CF IL2ZeroDb Zero point clamping 7 9 3 2 Phase phase voltage measurement VMMXU LN type LN prefix LN class Function block name VMMXU revision 1 V MMXU VMMXU Table 230 VMMXU Logical nod...

Page 321: ...plitude range range MX UL12RANG Mon UL12 Amplitude range q MX UL31 Mon Quality UL31 Amplitude magnitude of reported value q MX UL23 Mon Quality UL23 Amplitude magnitude of reported value q MX UL12 Mon...

Page 322: ...ta DO name DO type DA name FC T Signal Mon C md Description Mod a_dINC Oper ctlVal CO Mod Cmd Mode parameter for 61850 Oper origin orCat CO Mod Cmd Mode parameter for 61850 Oper origin orIdent CO Mod...

Page 323: ...Lim High High limit in of UBase rangeC hLim f CF UL3HiLim High limit in of UBase rangeC lLim f CF UL3LowLim Low limit in of UBase rangeC llLim f CF UL3LowLowLim Low Low limit in of UBase rangeC max f...

Page 324: ...al Mon C md Description Mod a_dINC Oper ctlVal CO Mod Cmd Mode parameter Oper origin orCat CO Mod Cmd Mode parameter Oper origin orIdent CO Mod Cmd Mode parameter Oper ctlNum CO Mod Cmd Mode parameter...

Page 325: ...IBase rangeC lLim f CF I2LowLim Low limit in of IBase rangeC llLim f CF I2LowLowLim Low Low limit in of IBase rangeC max f CF I2Max Maximum value in of IBase rangeC min f CF I2Min Minimum value in of...

Page 326: ...arameter stVal ST Mon Mode status parameter for 61850 q ST Mon Quality Mode status parameter for 61850 t ST Mon Timestamp Mode status parameter for 61850 Beh a_dINS stVal ST Beh Mon Behaviour paramete...

Page 327: ...CVal mag f SV Substituted value range MX U2RANG Mon U2 Amplitude range range MX U1RANG Mon U1 Amplitude range range MX 3U0RANG Mon 3U0 Amplitude range q MX U2 Mon Quality U2 Amplitude magnitude of rep...

Page 328: ...50 q ST Mon Quality Mode status parameter for 61850 t ST Mon Timestamp Mode status parameter for 61850 Beh a_dINS stVal ST Beh Mon Behaviour parameter for 61850 q ST Beh Mon Quality Behaviour paramete...

Page 329: ...r IEC61850 Oper Test CO Cmd Command parameter for IEC61850 Oper Check CO Cmd Command parameter for IEC61850 RsTrvTm v1_dSPC Oper ctlVal CO Cmd Command parameter for IEC61850 Oper origin orCat CO Cmd C...

Page 330: ...of CB operations exceeds alarm limit OpNumLO v1_dSPS stVal ST OPERLO Mon Number of CB operations exceeds lockout limit q ST OPERLO Mon Quality Number of CB operations exceeds lockout limit t ST OPERL...

Page 331: ...closed position q ST CLOSEPOS Mon Quality CB is in closed position t ST CLOSEPOS Mon Timestamp CB is in closed position CBLifAlm v1_dSPS stVal ST CBLIFEAL Mon Remaining life of CB reduced to Life alar...

Page 332: ...ver CB open travel time PresAlm v3_dSPS stVal ST GPRESALM Mon Pressure below alarm level q ST GPRESALM Mon Quality Pressure below alarm level t ST GPRESALM Mon Timestamp Pressure below alarm level OpC...

Page 333: ...n Pressure below alarm level q ST PRES_ALM Mon Quality Pressure below alarm level t ST PRES_ALM Mon Timestamp Pressure below alarm level TmpAlm a_dSPS stVal ST TEMP_ALM Mon Temperature above alarm lev...

Page 334: ...nal Mon C md Description Mod a_dINC Oper ctlVal CO Mod Cmd Mode parameter for 61850 Oper origin orCat CO Mod Cmd Mode parameter for 61850 Oper origin orIdent CO Mod Cmd Mode parameter for 61850 Oper c...

Page 335: ...alue Tmp b_dMV mag f MX TEMP Mon Temperature of the insulation medium q MX TEMP Mon Quality Temperature of the insulation medium t MX TEMP Mon Timestamp Temperature of the insulation medium LORs v1_dS...

Page 336: ...Mode status parameter for 61850 Beh a_dINS stVal ST Beh Mon Behaviour parameter for 61850 q ST Beh Mon Quality Behaviour parameter for 61850 t ST Beh Mon Timestamp Behaviour parameter for 61850 BlkCl...

Page 337: ...n local mode process level OpCnt b_dINS stVal ST CNT_VAL Mon Operation counter value q ST CNT_VAL Mon Quality Operation counter value t ST CNT_VAL Mon Timestamp Operation counter value Pos c_dDPC stVa...

Page 338: ...arameter for 61850 Oper origin orIdent CO Mod Cmd Mode parameter for 61850 Oper ctlNum CO Mod Cmd Mode parameter for 61850 Oper T CO Mod Cmd Mode parameter for 61850 Oper Test CO Mod Cmd Mode paramete...

Page 339: ...cked for open commands q ST OP_BLKD Mon Quality Indication that the function is blocked for open commands t ST OP_BLKD Mon Timestamp Indication that the function is blocked for open commands Loc a_dSP...

Page 340: ...lue Oper origin orIdent CO Cmd Special block command value Oper ctlNum CO Cmd Special block command value Oper T CO Cmd Special block command value Oper Test CO Cmd Special block command value Oper Ch...

Page 341: ...IPOSAL Mon Timestamp Alarm for tap in highest volt position EndPosL a_dSPS stVal ST LOPOSAL Mon Alarm for tap in lowest volt position q ST LOPOSAL Mon Quality Alarm for tap in lowest volt position t S...

Page 342: ...l HMI Oper origin orCat CO Cmd Command parameter for Local HMI Oper origin orIdent CO Cmd Command parameter for Local HMI Oper ctlNum CO Cmd Command parameter for Local HMI Oper T CO Cmd Command param...

Page 343: ...the position indication CLCnt v2_dMV mag f MX CLCNT_VAL Mon Remaining number of operations at rated load q MX CLCNT_VAL Mon Quality Remaining number of operations at rated load t MX CLCNT_VAL Mon Tim...

Page 344: ...ap position valWTr transInd ST Mon Tap position change in progress q ST TCPOS Mon Quality Integer value corresponding to actual tap position t ST TCPOS Mon Timestamp Integer value corresponding to act...

Page 345: ...for a command without an expected position change q ST CMDERRAL Mon Quality Alarm for a command without an expected position change t ST CMDERRAL Mon Timestamp Alarm for a command without an expected...

Page 346: ...arm that indicates a problem with the position indication t ST POSERRAL Mon Timestamp Alarm that indicates a problem with the position indication CLCnt v2_dMV mag f MX CLCNT_VAL Mon Remaining number o...

Page 347: ...on Internal parameter tag to handle 61850 mapping TagApp5 a_dDPS stVal ST Mon Internal parameter tag to handle 61850 mapping TagApp6 a_dDPS stVal ST Mon Internal parameter tag to handle 61850 mapping...

Page 348: ...al parameter tag to handle 61850 mapping TagBinOut2 a_dSPS stVal ST Mon Internal parameter tag to handle 61850 mapping q ST Mon Quality Internal parameter tag to handle 61850 mapping TagBinOut3 a_dSPS...

Page 349: ...instance 1 revision 0 VCTR GREC GOOSEVCTRRCV Table 243 GOOSEVCTRRCV Logical node data instance 1 DO name DO type DA name FC T Signal Mon C md Description In_LodAIm V10_dMV mag f MX Mon Imaginary part...

Page 350: ...condary side horizontal communication t MX Mon Timestamp Transformer reactance secondary side horizontal communication In_status V6_dINS stVal ST Mon VCTR Control word horizontal communication q ST Mo...

Page 351: ...on block to receive a measurand value GOOSEMVRCV LN type LN prefix LN class Function block name MVGREC instance 1 revision 0 MV GREC GOOSEMVRCV Table 246 GOOSEMVRCV Logical node data instance 1 DO nam...

Page 352: ...FC T Signal Mon C md Description TagBinOut a_dSPS stVal ST Mon Internal parameter tag to handle 61850 mapping q ST Mon Quality Internal parameter tag to handle 61850 mapping Section 8 1MRK 511 349 UEN...

Page 353: ...em and standard solution Benefits IEDs uses the customer model for communication Customer specific naming convention for communication can be used Other IEDs and station level equipment can be defined...

Page 354: ...e mapping is performed there are some requirements that must be fulfilled between the IED model and the customer model One attribute in the customer model can only be mapped to one attribute in the IE...

Page 355: ...y in the case of different operational states of the IED Functions When several LNs in the customer model are mapped to one function in the IED the Mod of the function will affect all the customer LNs...

Page 356: ...350...

Page 357: ...tion service data unit AWG American Wire Gauge standard BBP Busbar protection BFOC 2 5 Bayonet fibre optic connector BFP Breaker failure protection BI Binary input BIM Binary input module BOM Binary o...

Page 358: ...Common Format for Transient Data Exchange format for Disturbance recorder according to IEEE ANSI C37 111 1999 IEC60255 24 Contra directional Way of transmitting G 703 over a balanced line Involves fou...

Page 359: ...ult protection EPA Enhanced performance architecture ESD Electrostatic discharge F SMA Type of optical fibre connector FAN Fault number FCB Flow control bit Frame count bit FOX 20 Modular 20 channel t...

Page 360: ...ements for protective current transformers for transient performance IEC 60870 5 103 Communication standard for protection equipment A serial master slave protocol for point to point communication IEC...

Page 361: ...gh the data link layer 2 Ingression protection according to IEC 60529 IP 20 Ingression protection according to IEC 60529 level 20 IP 40 Ingression protection according to IEC 60529 level 40 IP 54 Ingr...

Page 362: ...Pulse code modulation PCM600 Protection and control IED manager PC MIP Mezzanine card standard PMC PCI Mezzanine card POR Permissive overreach POTT Permissive overreach transfer trip Process bus Bus o...

Page 363: ...OF Status of fault SPA Str mberg Protection Acquisition SPA a serial master slave protocol for point to point and ring communication SRY Switch for CB ready condition ST Switch or push button to trip...

Page 364: ...Mesures BIPM which forms the basis of a coordinated dissemination of standard frequencies and time signals UTC is derived from International Atomic Time TAI by the addition of a whole number of leap s...

Page 365: ...359...

Page 366: ...act us ABB AB Substation Automation Products SE 721 59 V ster s Sweden Phone 46 0 21 32 50 00 Fax 46 0 21 14 69 18 www abb com substationautomation 1MRK 511 349 UEN Copyright 2015 ABB All rights reser...

Reviews: