Section 8
IEC 60870-5-103 communication
engineering
8.1
Engineering in PCM600
The Application Configuration tool (ACT) and the Parameter Setting tool (PST) in
PCM600 are used to configure the communication for IEC 60870-5-103 protocol.
1.
Add the desired IEC 60870-5-103 function blocks to the application
configuration in the Application Configuration tool.
2.
Connect the outputs of desired protection and monitoring function in the
application configuration to the inputs of the corresponding IEC 60870-5-103
function block.
3.
Set the function type and desired information number, where an information
number must be supplied, for each IEC 60870-5-103 function block instance
in the Parameter Setting tool.
4.
Set the general communication for IEC 60870-5-103 and time
synchronization parameters in the Parameter Setting tool.
See the Communication protocol manual for IEC 60870-5-103 for more
information about the IEC 60870-5-103 implementation in .
The COM05 module is equipped with an optical serial and RS485
serial communication interface. IEC60870-5-103 can be
communicated from either of these serial interfaces. The user must
select in PST which interface to use.