15.7.2
Single point indication related signals combining function block
INDCOMBSPQT
The value of single point input (SP_IN) is copied to the value part of the SP_OUT output.
The TIME input is copied to the time part of the SP_OUT output. State input bits are
copied to the corresponding state part of the SP_OUT output. If the state or value on the
SP_OUT output changes, the Event bit in the state part is toggled.
INDCOMBSPQT can propagate the quality, the value and the time stamps of the signals
via IEC61850.
15.7.2.1
Function block
INDCOMBSPQT
SP_IN*
TIME*
BLOCKED*
SUBST*
INVALID*
TEST*
SP_OUT
IEC15000146.vsd
IEC15000146 V1 EN
Figure 160:
INDCOMBSPQT function block
15.7.2.2
Signals
Table 309:
INDCOMBSPQT Input signals
Name
Type
Default
Description
SP_IN
BOOLEAN
0
Single point indication
TIME
GROUP
SIGNAL
0
Timestamp
BLOCKED
BOOLEAN
0
Blocked for update
SUBST
BOOLEAN
0
Substituted
INVALID
BOOLEAN
0
Invalid value
TEST
BOOLEAN
0
Testmode
Table 310:
INDCOMBSPQT Output signals
Name
Type
Description
SP_OUT
BOOLEAN
Single point indication
1MRK 511 365-UUS A
Section 15
Logic
Phasor measurement unit RES670 2.1 ANSI
443
Technical manual
Summary of Contents for Relion 670 Series RES670
Page 1: ...Relion 670 series Phasor measurement unit RES670 2 1 ANSI Technical manual ...
Page 2: ......
Page 36: ...30 ...
Page 76: ...70 ...
Page 106: ...100 ...
Page 150: ...144 ...
Page 274: ...268 ...
Page 326: ...320 ...
Page 356: ...350 ...
Page 382: ...376 ...
Page 416: ...410 ...
Page 590: ...584 ...
Page 604: ...598 ...
Page 694: ...688 ...
Page 756: ...750 ...
Page 834: ...828 ...
Page 836: ...830 ...
Page 876: ...870 ...
Page 886: ...880 ...
Page 887: ...881 ...