![ABB RELION 650 SERIES Technical Manual Download Page 830](http://html.mh-extra.com/html/abb/relion-650-series/relion-650-series_technical-manual_2122830.webp)
PID-3406-SETTINGS v5
Table 618:
SMAI2 Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
GlobalBaseSel
1 - 12
-
1
1
Selection of one of the Global Base
Value groups
DFTReference
InternalDFTRef
DFTRefGrp1
DFTRefGrp2
DFTRefGrp3
DFTRefGrp4
DFTRefGrp5
DFTRefGrp6
DFTRefGrp7
DFTRefGrp8
DFTRefGrp9
DFTRefGrp10
DFTRefGrp11
DFTRefGrp12
External DFT ref
-
-
InternalDFTRef
DFT reference
ConnectionType
Ph-N
Ph-Ph
-
-
Ph-N
Input connection type
AnalogInputType
Voltage
Current
-
-
Voltage
Analog input signal type
Table 619:
SMAI2 Non group settings (advanced)
Name
Values (Range)
Unit
Step
Default
Description
Negation
Off
NegateN
Negate3Ph
NeN
-
-
Off
Negation
MinValFreqMeas
5 - 200
%
1
10
Limit for frequency calculation in % of
UBase
19.8.5
Operation principle
SEMOD55746-4 v13
Every Signal matrix for analog inputs function (SMAI) can receive four analog
signals (three phases and one neutral or residual value), either voltage or current,
see figure
. SMAI outputs give information about every aspect
of the 3ph analog signals acquired (phase angle, RMS value, frequency and
frequency derivates etc. – 244 values in total). The BLOCK input will force all
outputs to value zero if BLOCK is TRUE (1).
System phase rotation and frequency are defined using the
PhaseRotation
and
Frequency
settings in the primary system values PRIMVAL function. Logic 1 in
the REVROT input to the SMAI function means that the phase rotation is changed
relative to the set
PhaseRotation
in PRIMVAL.
The output signal AI1 to AI4 are single phase outputs which directly represent the
four inputs GRPxL1, GRPxL2, GRPxL3 and GRPxN, x=1-12. GxN (x = 1-12) is
always calculated residual sum from the first three inputs. A3P is grouped, three-
phase information containing all relevant information about four connected inputs.
Section 19
1MRK 506 382-UEN A
Basic IED functions
824
Line distance protection REL650 2.2 IEC
Technical manual
Summary of Contents for RELION 650 SERIES
Page 1: ...RELION 650 SERIES Line distance protection REL650 Version 2 2 Technical manual ...
Page 2: ......
Page 46: ...40 ...
Page 56: ...50 ...
Page 164: ...158 ...
Page 264: ...258 ...
Page 304: ...298 ...
Page 320: ...314 ...
Page 338: ...332 ...
Page 438: ...432 ...
Page 468: ...462 ...
Page 534: ...528 ...
Page 646: ...640 ...
Page 660: ...654 ...
Page 676: ...670 ...
Page 800: ...794 ...
Page 836: ...830 ...
Page 890: ...884 ...
Page 894: ...888 ...
Page 940: ...934 ...
Page 941: ...935 ...