5.5.2
LED configuration alternatives
5.5.2.1
Functionality
GUID-1A03E0EF-C10F-4797-9D9F-5CCA86CA29EB v5
The function blocks LEDGEN and GRP1_LEDx, GRP2_LEDx and GRP3_LEDx
(x=1-15) controls and supplies information about the status of the indication LEDs.
The input and output signals of the function blocks are configured with PCM600.
The input signal for each LED is selected individually using SMT or ACT. Each
LED is controlled by the GRPn_LEDx (n=1-3) function block that controls the
color and the operating mode.
Each indication LED on local HMI can be set individually to operate in 6 different
sequences; two as follow type and four as latch type. Two of the latching sequence
types are intended to be used as a protection indication system, either in collecting
or restarting mode, with reset functionality. The other two are intended to be used
as signalling system in collecting mode with acknowledgment functionality.
5.5.2.2
Status LEDs
GUID-4822DF9C-E343-442B-B3F1-3FA8CD8DF234 v4
There are three status LEDs above the LCD in front of the IED: green, yellow and
red.
The green LED has a fixed function that presents the healthy status of the IED. The
yellow and red LEDs are user configured. The yellow LED can be used to indicate
that a disturbance report is triggered (steady) or that the IED is in test mode
(flashing). The red LED can be used to indicate a trip command.
Here is a typical configuration of the status LEDs:
•
Green LED: unlit > no power; blinking > startup or abnormal situation (IED is
not in service); steady > IED is in service
•
Yellow LED: unlit > no attention required; blinking > IED is in Testmode
(IED is not in normal service); steady > at least one of the signals configured
to turn the yellow LED on has been active
•
Red LED: unlit > no attention required; blinking > user performs a common
write from PCM600; steady > at least one of the signals configured to turn the
red LED on has been active
The yellow and red status LEDs are configured in the disturbance recorder
function, DRPRDRE, by connecting a start or trip signal from the actual function
to a BxRBDR binary input function block using the PCM600, and configuring the
setting to
Off
,
Start
or
Trip
for that particular signal.
5.5.2.3
Indication LEDs
Operating modes
GUID-B67F1ED3-900B-4D34-8EEB-A3005999CE50 v4
Collecting mode
Section 5
1MRK 506 382-UEN A
Local Human-Machine-Interface LHMI
76
Line distance protection REL650 2.2 IEC
Technical manual
Summary of Contents for RELION 650 SERIES
Page 1: ...RELION 650 SERIES Line distance protection REL650 Version 2 2 Technical manual ...
Page 2: ......
Page 46: ...40 ...
Page 56: ...50 ...
Page 164: ...158 ...
Page 264: ...258 ...
Page 304: ...298 ...
Page 320: ...314 ...
Page 338: ...332 ...
Page 438: ...432 ...
Page 468: ...462 ...
Page 534: ...528 ...
Page 646: ...640 ...
Page 660: ...654 ...
Page 676: ...670 ...
Page 800: ...794 ...
Page 836: ...830 ...
Page 890: ...884 ...
Page 894: ...888 ...
Page 940: ...934 ...
Page 941: ...935 ...