The IRIG-B module also takes care of IEEE1344 messages that are sent by IRIG-B
clocks, as IRIG-B previously did not have any year information. IEEE1344 is
compatible with IRIG-B and contains year information and information of the
time-zone.
19.1.3.4
Process bus IEC/UCA 61850-9-2LE synchronization
GUID-6E384BDB-5598-4108-99B4-0B4A4E1828B2 v4
When process bus communication (IEC/UCA 61850-9-2LE protocol) is used, it is
essential that the merging units are synchronized with the hardware time of the IED
(see Technical manual, section
Design of the time system (clock synchronization
) ).
To achieve this, PTP, PPS or IRIG-B can be used depending of the facilities of the
merging unit.
If the merging unit supports PTP, use PTP. If PTP is used in the IED and the
merging unit cannot be synchronized from the IED, then use GPS-based clocks to
provide PTP synch as well as sync to the merging unit.
If synchronization of the IED and the merging unit is based on GPS, set the
parameter
LostSyncMode
to
BlockOnLostUTC
in order to provide a block of
protection functions whenever the global common time is lost.
If PTP is not used, use the same synchronization method for the
HwSyncSrc
as the
merging unit provides. For instance, if the merging unit provides PPS as
synchronization, use PPS as
HwSyncSrc
. If LDCM in GPS-mode is used, that is,
the hardware and software clocks are connected to each other,
HwSyncSrc
is not
used and other means to synchronize the merging unit to the IED is required. For
instance,
FineSyncSource
is set to the same source that the merging unit uses.
19.1.3.5
Precision Time Protocol (PTP)
GUID-4F2B68B8-CCC8-4173-A644-D1674D3146F8 v1
PTP according to IEEE 1588-2008 and specifically its profile IEC/IEEE 61850-9-3
for power utility automation is a synchronization method that differs from SNTP,
for instance, by providing much better accuracy and by being not predefined. By
not predefined is meant that it is not mandatory to have a predefined
synchronization tree, as the master (Grand Master) may shift.
Consider instead PTP as a synchronization grouping, i.e. all devices connected to
the PTP group will be synchronized to the same source or, if there is no external
source the group will at least maintain a common time. The group is synchronized
by connecting one or more “Grand Master” clocks to it. The clocks can be part of
the devices in the group or be specialized synchronization devices, as for instance a
GPS clock or similar. If several synchronization devices are connected to the
group, the “Best Master Algorithm” in the PTP protocol will assure that only one is
the “Grand Master”. The IED can act as a synchronization device and supply any
synchronization source (like SNTP, IRIG-B, SPA etc) as clock input, that will
synchronize the whole PTP group if there is no better source available in the group.
The IED can be connected to several groups and thereby connect them to each
other, by acting as a “Boundary Clock”. If PTP is “On” on several Access Points,
Section 19
1MRK 506 382-UEN A
Basic IED functions
808
Line distance protection REL650 2.2 IEC
Technical manual
Summary of Contents for RELION 650 SERIES
Page 1: ...RELION 650 SERIES Line distance protection REL650 Version 2 2 Technical manual ...
Page 2: ......
Page 46: ...40 ...
Page 56: ...50 ...
Page 164: ...158 ...
Page 264: ...258 ...
Page 304: ...298 ...
Page 320: ...314 ...
Page 338: ...332 ...
Page 438: ...432 ...
Page 468: ...462 ...
Page 534: ...528 ...
Page 646: ...640 ...
Page 660: ...654 ...
Page 676: ...670 ...
Page 800: ...794 ...
Page 836: ...830 ...
Page 890: ...884 ...
Page 894: ...888 ...
Page 940: ...934 ...
Page 941: ...935 ...