Phase currents (amplitude and angle) are available on the outputs and each
amplitude output has a corresponding supervision level output (ILx_RANG). The
supervision output signal is an integer in the interval 0-4, see
section
.
14.1.7.4
Phase-phase and phase-neutral voltage measurements VMMXU,
VNMMXU
SEMOD54417-268 v6
The voltage function must be connected to three-phase voltage input in the
configuration tool to be operable. Voltages are handled in the same way as currents
when it comes to class 0.5 calibrations, see above.
The voltages (phase-to-earth or phase-to-phase voltage, amplitude and angle) are
available on the outputs and each amplitude output has a corresponding supervision
level output (ULxy_RANG). The supervision output signal is an integer in the
interval 0-4, see section
.
14.1.7.5
Voltage and current sequence measurements VMSQI, CMSQI
SEMOD54417-299 v6
The measurement functions must be connected to three-phase current (CMSQI) or
voltage (VMSQI) input in the configuration tool to be operable. No outputs, other
than X_RANG, are calculated within the measuring blocks and it is not possible to
calibrate the signals. Input signals are obtained from the pre-processing block and
transferred to corresponding output.
Positive, negative and three times zero sequence quantities are available on the
outputs (voltage and current, amplitude and angle). Each amplitude output has a
corresponding supervision level output (X_RANGE). The output signal is an
integer in the interval 0-4, see section
14.1.8
Technical data
M12386-1 v15
Table 396:
Power system measurement CVMMXN technical data
Function
Range or value
Accuracy
Frequency
(0.95-1.05) x f
r
±
2.0 mHz
Voltage
(10 to 300) V
±
0.3% of U at U
≤
50 V
±
0.2% of U at U
>
50 V
Current
(0.1-4.0) x I
r
±
0.8% of I at 0.1 x I
r
<
I
<
0.2 x I
r
±
0.5% of I at 0.2 x I
r
<
I
<
0.5 x I
r
±
0.2% of I at 0.5 x I
r
<
I
<
4.0 x I
r
Active power, P
(10 to 300) V
(0.1-4.0) x I
r
±
0.5% of S
r
at S
≤
0.5 x S
r
±
0.5% of S at S
>
0.5 x S
r
(100 to 220) V
(0.5-2.0) x I
r
cos
φ
<
0.7
±
0.2% of P
Table continues on next page
Section 14
1MRK 506 382-UEN A
Monitoring
562
Line distance protection REL650 2.2 IEC
Technical manual
Summary of Contents for RELION 650 SERIES
Page 1: ...RELION 650 SERIES Line distance protection REL650 Version 2 2 Technical manual ...
Page 2: ......
Page 46: ...40 ...
Page 56: ...50 ...
Page 164: ...158 ...
Page 264: ...258 ...
Page 304: ...298 ...
Page 320: ...314 ...
Page 338: ...332 ...
Page 438: ...432 ...
Page 468: ...462 ...
Page 534: ...528 ...
Page 646: ...640 ...
Page 660: ...654 ...
Page 676: ...670 ...
Page 800: ...794 ...
Page 836: ...830 ...
Page 890: ...884 ...
Page 894: ...888 ...
Page 940: ...934 ...
Page 941: ...935 ...