Time Integration
with Retain
BLOCK
ACCTIME
RESET
IN
tWarning
tAlarm
OVERFLOW
WARNING
ALARM
q
-1
a>b
a
b
a>b
a
b
a>b
a
b
AND
AND
AND
q
-1
= unit delay
IEC13000290-2-en.vsd
999 999 s
IEC13000290 V2 EN-US
Figure 270:
TEIGAPC logics
The main features of TEIGAPC
•
Applicable to long time integration up to 999 999.9 seconds
•
Supervision of overflow
•
Possibility to define a warning and an alarm with the resolution of 10
milliseconds
•
Retain the integration value
•
Possibilities for blocking and reset of the total integrated time
•
Report of the integrated time
13.13.3
Function block
GUID-6D50A060-7751-405B-AEC1-FAE942EBDA64 v2
TEIGAPC
BLOCK
IN
RESET
WARNING
ALARM
OVERFLOW
ACCTIME
IEC14000014-1-en.vsd
IEC14000014 V1 EN-US
Figure 271:
TEIGAPC function block
13.13.4
Signals
PID-6836-INPUTSIGNALS v2
Table 352:
TEIGAPC Input signals
Name
Type
Default
Description
BLOCK
BOOLEAN
0
Freeze the integration and block the other outputs
IN
BOOLEAN
0
The input signal that is used to measure the
elapsed time, when its value is high
RESET
BOOLEAN
0
Reset the integration time
Section 13
1MRK 506 382-UEN A
Logic
518
Line distance protection REL650 2.2 IEC
Technical manual
Summary of Contents for RELION 650 SERIES
Page 1: ...RELION 650 SERIES Line distance protection REL650 Version 2 2 Technical manual ...
Page 2: ......
Page 46: ...40 ...
Page 56: ...50 ...
Page 164: ...158 ...
Page 264: ...258 ...
Page 304: ...298 ...
Page 320: ...314 ...
Page 338: ...332 ...
Page 438: ...432 ...
Page 468: ...462 ...
Page 534: ...528 ...
Page 646: ...640 ...
Page 660: ...654 ...
Page 676: ...670 ...
Page 800: ...794 ...
Page 836: ...830 ...
Page 890: ...884 ...
Page 894: ...888 ...
Page 940: ...934 ...
Page 941: ...935 ...