AND
BLOCK
IRVBLK
t
tPickUpRev
t
tPickUpRev
t
10 ms
IRV
CurrRev = On
t
tDelayRev
IRVL
IEC09000031-4-en.vsd
IEC09000031 V4 EN-US
Figure 235:
Simplified logic diagram for current reversal
12.5.6.3
Weak-end infeed logic
M13929-24 v10
The weak-end infeed function can be set to send only an echo signal (
WEI=Echo
)
or an echo signal and a trip signal (
WEI=Echo & Trip
). The corresponding logic
diagrams are depicted in Figure
.
The weak-end infeed logic uses normally a reverse and a forward direction
element, connected to WEIBLK2 via an OR-gate. If neither the forward nor the
reverse directional measuring element is activated during the last 200 ms, the
weak-end infeed logic echoes back the received permissive signal as shown in
Figure
and Figure
. The weak-end infeed logic also echoes the received
permissive signal when CBOPEN is high (local breaker opens) prior to faults
appeared at the end of line.
If the forward or the reverse directional measuring element is activated during the
last 200 ms, the fault current is sufficient for the IED to detect the fault with the
earth fault function that is in operation.
1MRK 506 382-UEN A
Section 12
Scheme communication
Line distance protection REL650 2.2 IEC
459
Technical manual
Summary of Contents for RELION 650 SERIES
Page 1: ...RELION 650 SERIES Line distance protection REL650 Version 2 2 Technical manual ...
Page 2: ......
Page 46: ...40 ...
Page 56: ...50 ...
Page 164: ...158 ...
Page 264: ...258 ...
Page 304: ...298 ...
Page 320: ...314 ...
Page 338: ...332 ...
Page 438: ...432 ...
Page 468: ...462 ...
Page 534: ...528 ...
Page 646: ...640 ...
Page 660: ...654 ...
Page 676: ...670 ...
Page 800: ...794 ...
Page 836: ...830 ...
Page 890: ...884 ...
Page 894: ...888 ...
Page 940: ...934 ...
Page 941: ...935 ...