of the protection including a channel transmission time, can be achieved. This short
operate time enables rapid autoreclosing function after the fault clearance.
The communication logic module for directional residual current protection
enables blocking as well as permissive under/overreaching, and unblocking
schemes. The logic can also be supported by additional logic for weak-end infeed
and current reversal, included in Current reversal and weak-end infeed logic for
residual overcurrent protection (ECRWPSCH) function.
12.4.3
Function block
M13924-3 v5
IEC06000288-2-en.vsd
ECPSCH
BLOCK
BLKTR
BLKCS
CSBLK
CACC
CSOR
CSUR
CR
CRG
TRIP
CS
CRL
LCG
IEC06000288 V2 EN-US
Figure 231:
ECPSCH function block
12.4.4
Signals
PID-3581-INPUTSIGNALS v7
Table 264:
ECPSCH Input signals
Name
Type
Default
Description
BLOCK
BOOLEAN
0
Block of function
BLKTR
BOOLEAN
0
Signal for blocking trip due to communication
logic
BLKCS
BOOLEAN
0
Signal for blocking CS in Overreach and Blocking
schemes
CSBLK
BOOLEAN
0
Reverse residual overcurrent signal for Carrier
Send
CACC
BOOLEAN
0
Signal to be used for tripping by Communication
Scheme
CSOR
BOOLEAN
0
Overreaching residual overcurrent signal for
Carrier Send
CSUR
BOOLEAN
0
Underreaching residual overcurrent signal for
Carrier Send
CR
BOOLEAN
0
Carrier Receive for Communication Scheme
Logic
CRG
BOOLEAN
0
Carrier guard signal received
Section 12
1MRK 506 382-UEN A
Scheme communication
450
Line distance protection REL650 2.2 IEC
Technical manual
Summary of Contents for RELION 650 SERIES
Page 1: ...RELION 650 SERIES Line distance protection REL650 Version 2 2 Technical manual ...
Page 2: ......
Page 46: ...40 ...
Page 56: ...50 ...
Page 164: ...158 ...
Page 264: ...258 ...
Page 304: ...298 ...
Page 320: ...314 ...
Page 338: ...332 ...
Page 438: ...432 ...
Page 468: ...462 ...
Page 534: ...528 ...
Page 646: ...640 ...
Page 660: ...654 ...
Page 676: ...670 ...
Page 800: ...794 ...
Page 836: ...830 ...
Page 890: ...884 ...
Page 894: ...888 ...
Page 940: ...934 ...
Page 941: ...935 ...