![ABB RELION 650 SERIES Technical Manual Download Page 429](http://html.mh-extra.com/html/abb/relion-650-series/relion-650-series_technical-manual_2122429.webp)
11.7.4
Signals
SEMOD55883-1 v2
PID-4139-INPUTSIGNALS v12
Table 237:
DPGAPC Input signals
Name
Type
Default
Description
OPEN
BOOLEAN
0
Open indication
CLOSE
BOOLEAN
0
Close indication
VALID
BOOLEAN
0
Valid indication
PID-4139-OUTPUTSIGNALS v11
Table 238:
DPGAPC Output signals
Name
Type
Description
POSITION
INTEGER
Double point indication
11.7.5
Settings
ABBD8E283863 v3
The function does not have any parameters available in the local HMI or PCM600.
11.7.6
Operation principle
SEMOD55861-5 v7
When receiving the input signals, DPGAPC sends the signals over IEC 61850-8-1
to the systems, equipment or functions that requests and thus subscribes on these
signals. To be able to get the signals into other systems, equipment or functions,
one must use other tools, described in the Engineering manual, and define which
function block in which systems, equipment or functions should receive this
information.
More specifically, DPGAPC function reports a combined double point position
indication output POSITION, by evaluating the value and the timestamp attributes
of the inputs OPEN and CLOSE, together with the logical input signal VALID.
When the input signal VALID is active, the values of the OPEN and CLOSE inputs
determine the two-bit integer value of the output POSITION. The timestamp of the
output POSITION will have the latest updated timestamp of the inputs OPEN and
CLOSE.
When the input signal VALID is inactive, DPGAPC function forces the position to
intermediated state.
When the value of the input signal VALID changes, the timestamp of the output
POSITION will be updated as the time when DPGAPC function detects the
change.
Refer to Table
for the description of the input-output relationship in terms of
the value and the quality attributes.
1MRK 506 382-UEN A
Section 11
Control
Line distance protection REL650 2.2 IEC
423
Technical manual
Summary of Contents for RELION 650 SERIES
Page 1: ...RELION 650 SERIES Line distance protection REL650 Version 2 2 Technical manual ...
Page 2: ......
Page 46: ...40 ...
Page 56: ...50 ...
Page 164: ...158 ...
Page 264: ...258 ...
Page 304: ...298 ...
Page 320: ...314 ...
Page 338: ...332 ...
Page 438: ...432 ...
Page 468: ...462 ...
Page 534: ...528 ...
Page 646: ...640 ...
Page 660: ...654 ...
Page 676: ...670 ...
Page 800: ...794 ...
Page 836: ...830 ...
Page 890: ...884 ...
Page 894: ...888 ...
Page 940: ...934 ...
Page 941: ...935 ...