11.4.7.2
Function block
M13500-3 v5
SXCBR
BLOCK
LR_SWI
OPEN
CLOSE
BL_OPEN
BL_CLOSE
BL_UPD
POSOP EN
POSCLOSE
CBOPCAP
TR_OPEN
TR_CLOSE
RS_CNT
EEH_WARN
EEH_ALM
XIN*
XPOS
EXE_OP
EXE_CL
OP_BLKD
CL_BLKD
UPD_BLKD
OPENP OS
CLOSEPOS
TR_POS
CNT_VAL
L_CAUSE
EEHEALTH
CBOPCAP
IEC05000338-4-en.vsdx
IEC05000338 V5 EN-US
Figure 203:
SXCBR function block
11.4.7.3
Signals
PID-6799-INPUTSIGNALS v2
Table 223:
SXCBR Input signals
Name
Type
Default
Description
BLOCK
BOOLEAN
0
Block of function
LR_SWI
BOOLEAN
0
Local/Remote switch indication from switchyard
OPEN
BOOLEAN
0
Pulsed signal used to immediately open the
switch
CLOSE
BOOLEAN
0
Pulsed signal used to immediately close the
switch
BL_OPEN
BOOLEAN
0
Signal to block the open command
BL_CLOSE
BOOLEAN
0
Signal to block the close command
BL_UPD
BOOLEAN
0
Steady signal for block of the position updating
POSOPEN
BOOLEAN
0
Signal for open position of apparatus from I/O
POSCLOSE
BOOLEAN
0
Signal for close position of apparatus from I/O
CBOPCAP
INTEGER
3
Breaker operating capability 1 = None, 2 = O, 3 =
CO, 4 = OCO, 5 = COCO, 6+ = More
TR_OPEN
BOOLEAN
0
Signal for open position of truck from I/O
TR_CLOSE
BOOLEAN
0
Signal for close position of truck from I/O
RS_CNT
BOOLEAN
0
Resets the operation counter
EEH_WARN
BOOLEAN
0
Warning from external equipment
EEH_ALM
BOOLEAN
0
Alarm from external equipment
XIN
GROUP
SIGNAL
-
Execution information from CSWI
Section 11
1MRK 506 382-UEN A
Control
404
Line distance protection REL650 2.2 IEC
Technical manual
Summary of Contents for RELION 650 SERIES
Page 1: ...RELION 650 SERIES Line distance protection REL650 Version 2 2 Technical manual ...
Page 2: ......
Page 46: ...40 ...
Page 56: ...50 ...
Page 164: ...158 ...
Page 264: ...258 ...
Page 304: ...298 ...
Page 320: ...314 ...
Page 338: ...332 ...
Page 438: ...432 ...
Page 468: ...462 ...
Page 534: ...528 ...
Page 646: ...640 ...
Page 660: ...654 ...
Page 676: ...670 ...
Page 800: ...794 ...
Page 836: ...830 ...
Page 890: ...884 ...
Page 894: ...888 ...
Page 940: ...934 ...
Page 941: ...935 ...